3.5.2.1.2 Grounding
Caution!
The functional ground (power supply pin 2 and ground connection) must be connected to the central
grounding point (e.g. control cabinet or system) via the shortest possible path with the lowest possible
resistance and with the largest possible wire cross section. This type of grounding is mandatory for
proper functionality.
For example, a copper strip must be attached to the ground connection
at a central grounding point of the control cabinet or system in which the
device is installed. The wire cross section should be as large as possible
(at least 2.5 mm²).
3.5.2.1.3 SDL4 In interface
The SDL4 In interface is a female RJ45 connector and operated with SDL4
transmission technology.
Information:
Hot plugging output devices on the interface for service purposes is supported by the hardware and
graphic drivers of approved operating systems.
A maximum of 500 mating cycles are specified for this interface.