Accessories
Automation Panel 9xD - Hygienic design User's manual V 1.80
137
9.7 Line filter
9.7.1 5AC804.MFLT-00
9.7.1.1 General information
Line filter 5AC804.MFLT-00 may be necessary to satisfy maritime requirements regarding conducted disturbances
in supply lines in accordance with the GL (Germanischer Lloyd) or DNVGL.
The line filter should be installed as close to the end device as possible; the supply line from the end device to the
line filter should be kept as short as possible.
9.7.1.2 Order data
Model number
Short description
Figure
Accessories
5AC804.MFLT-00
Line filter
9.7.1.3 Technical data
Information:
The following specified characteristic data, features and limit values are only valid for this accessory
and may differ from those of the complete system. The data specified for the complete system applies
to the complete system in which this accessory is installed, for example.
Model number
5AC804.MFLT-00
General information
Certifications
CE
Yes
UL
cULus E115267
Industrial control equipment
HazLoc
cULus HazLoc E180196
Industrial control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T4
1)
DNV GL
Temperature:
B
(0 - 55°C)
Humidity:
B
(up to 100%)
Vibration:
A
(0.7 g)
EMC:
B
(bridge and open deck)
2)
EAC
Product family certification
Terminal block
Connection cross section
With wire end sleeves
1.5 mm²
Flexible
0.2 to 1.5 mm²
Inflexible
0.2 to 2.5 mm²
Electrical properties
Nominal voltage
24 VDC -25% / +30%, SELV
3)
Nominal current
8 A
Overvoltage category per EN 61131-2
II
Operating conditions
Pollution degree per EN 61131-2
Pollution degree 2
Ambient conditions
Temperature
Operation
-25 to 65°C
Storage
-25 to 65°C
Transport
-25 to 65°C
Mechanical properties
Housing
Material
Galvanized plate