Accessories
130
Automation Panel 9xD - Hygienic design User's manual V 1.80
9.3 Terminal block power supply
9.3.1 0TB103.9x
9.3.1.1 Order data
Model number
Short description
Figure
Accessories
0TB103.9
Connector 24 VDC - 3-pin, female - Screw clamp terminal block
3.31 mm²
0TB103.91
Connector 24 VDC - 3-pin, female - Cage clamp terminal block
3.31 mm²
9.3.1.2 Technical data
Information:
The following specified characteristic data, features and limit values are only valid for this accessory
and may differ from those of the complete system. The data specified for the complete system applies
to the complete system in which this accessory is installed, for example.
Model number
0TB103.9
0TB103.91
General information
Certifications
CE
Yes
UL
cULus E115267
Industrial control equipment
HazLoc
cULus HazLoc E180196
Industrial control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T4
1)
DNV GL
Temperature:
B
(0 - 55°C)
Humidity:
B
(up to 100%)
Vibration:
A
(0.7 g)
EMC:
B
(bridge and open deck)
2)
KR
Yes
EAC
Yes
Terminal block
Note
Protected against vibration by the screw flange
Nominal data per UL
Number of pins
3 (female)
Type of terminal block
Screw clamp terminal block variant
Cage clamp terminal block variant
3)
Cable type
Only copper wires (no aluminum wires!)
Pitch
5.08 mm
Connection cross section
AWG wire
26 to 14 AWG
26 to 12 AWG
Wire end sleeves with plastic covering
0.20 to 1.50 mm²
Solid wires
0.20 to 2.50 mm²
Fine-stranded wires
0.20 to 1.50 mm²
0.20 to 2.50 mm²
With wire end sleeves
0.20 to 1.50 mm²
Tightening torque
0.4 Nm
-
Electrical properties
Nominal voltage
300 V
Nominal current
4)
10 A / contact
Contact resistance
≤5 mΩ
Operating conditions
Pollution degree per EN 61131-2
Pollution degree 2
Table 50: 0TB103.9, 0TB103.91 - Technical data
1)
Yes, but applies only if all components installed in the complete system have this certification and the complete system bears the corresponding mark.
2)
Yes, but applies only if all components installed in the complete system have this certification and are listed on the associated DNV GL certificate for the
product family.
3)
The cage clamp terminal block cannot be used side by side.
4)
The respective limit data of the I/O modules must be taken into account!