Technical data
4.1.3.3 Spacing for air circulation
To ensure sufficient air circulation, a specified clearance must be provided above, below, to the side and behind
the device. For the minimum specified clearance, see the following diagrams. This is valid for all variants.
Information:
The following figure and table exclusively show the thermal view of the complete system. If additional
space is required for operating or servicing the device , this must be taken into account during instal-
lation.
Legend
1)
Air outlet
2)
Air inlet
Name
Dimension
Name
Dimension
S1
≥20
S2
≥50
S3
≥50
S4
≥50
Caution!
The specified spacing for air circulation is based on worst-case operation at the maximum specified
ambient temperature. The maximum specified ambient temperature is not permitted to be exceeded!
If the spacing specifications for air circulation cannot be observed, then the maximum specified tem-
peratures for the temperature sensors (see
"Temperature sensor positions" on page 32
) must be
monitored by the user and appropriate measures taken if they are exceeded.
28
Automation Panel 9x3 User's manual 2.01