X20 system modules • Bus controllers System modules • X20PS9402
578
X20 system User's Manual 3.10
4.6.4 X20PS9402
4.6.4.1 General information
The supply module is used together with an X20 bus controller. It is equipped with a feed for the bus controller,
the X2X Link and the internal I/O supply.
The module is designed to supply power for smaller X20 systems. Potential groups are able to be formed. An
expansion or redundancy of the X2X Link with the X20PS3300 or X20PS3310 supply module is not possible.
Expansion of the X20 system with a bus transmitter is not permitted either.
•
Supply for the bus controller, X2X Link and internal I/O supply
•
Low-cost supply module for small X20 system
•
Feed and bus controller / X2X Link supply not electrically isolated
•
Expansion or redundancy of bus controller / X2X Link supply not possible by operating multiple supply
modules simultaneously
4.6.4.2 Order data
Model number
Short description
Figure
System modules for bus controllers
X20PS9402
X20 supply module, for bus controller and internal I/O supply,
X2X Link supply, supply not electrically isolated
Required accessories
System modules for bus controllers
X20BB80
X20 bus base, for X20 base module (BC, HB, etc.) and X20 pow-
er supply module, X20 end plates X20AC0SL1/X20AC0SR1 (left
and right) included
System modules for expandable bus controllers
X20BB81
X20 bus base, for X20 base module (BC, HB, etc.) and X20
power supply module, with one expansion slot for an X20 add-
on module (IF, HB, etc.), X20 locking plates (left and right)
X20AC0SL1/X20AC0SR1 included
X20BB82
X20 bus base, for X20 base module (BC, HB, etc.) and X20
power supply module, with 2 expansion slots for 2 X20 add-
on modules (IF, HB, etc.), X20 locking plates (left and right)
X20AC0SL1/X20AC0SR1 included
Terminal blocks
X20TB12
X20 terminal block, 12-pin, 24 VDC keyed
Table 180: X20PS9402 - Order data
4.6.4.3 Technical data
Product ID
X20PS9402
Brief description
Power supply module
24 VDC supply module for bus controller, X2X Link supply and I/O
General information
B&R ID code
0xA389
Status indicators
Operating state, module status
Diagnostics
Module run/error
Yes, using status LED and software
Overload
Yes, using status LED and software
Power consumption
1)
Bus
1.44 W
Internal I/O
0.6 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
I/O feed - I/O supply
No
BC/X2X Link feed - BC/X2X Link supply
No
Certification
CE
Yes
cULus
Yes
cCSAus HazLoc Class 1 Division 2
Yes
ATEX Zone 2
Yes
KC
Yes
GOST-R
Yes
Bus controller / X2X Link supply input
Input voltage
24 VDC -15% / +20%
Input current
Max. 0.7 A
Fuse
Integrated, cannot be replaced
Table 181: X20PS9402 - Technical data