X20 system modules • Digital output modules • X20DO2633
1092
X20 system User's Manual 3.10
4.15.6.3 Technical data
Product ID
X20DO2633
Brief description
I/O module
2 digital outputs 12-240 VAC for 3-wire connections
General information
B&R ID code
0xAC39
Status indicators
I/O function per channel, operating state, module status
Diagnostics
Module run/error
Yes, using status LED and software
Outputs
Yes, using status LED and software
Power consumption
Bus
0.6 W
Internal I/O
-
External I/O
-
Additional power dissipation caused by the actua-
tors (resistive) [W]
1)
+6 W
Electrical isolation
Channel - Bus
Yes
Channel - Channel
No
Certification
CE
Yes
cULus
Yes
ATEX Zone 2
Yes
KC
Yes
GOST-R
Yes
Digital outputs
Design
Triac
Wiring
L switching
Nominal voltage
12 to 240 VAC
Rated frequency
47 to 63 Hz
Nominal output current
2.0 A
Total nominal current
4.0 A
Maximum current
Output current
2.5 A
Summation current
5.0 A
Connection type
3-wire connections
Zero-crossing detection
Yes
Minimum holding current I
H
15 mA
Leakage current
50 Hz: Max. 2.0 mA at 240 V
60 Hz: Max. 2.4 mA at 240 V
Residual voltage (on-state voltage)
1.5 V
Phase-angle control
Range
5 to 95%
Resolution
1%
Accuracy (60 to 240 VAC)
<100 μs
Voltage monitoring L - N
Yes
Additional functions
Open line detection
Overvoltage protection between L and N
Yes, Varistor
Output voltage
Minimum
10 VAC
Maximum
253 VAC
Isolation voltage
Terminal block - Bus
Tested at 2300 VAC (Rev. <E0 1500 VAC)
Terminal block - 24 V
Tested at 2300 VAC (Rev. <E0 2000 VAC)
Terminal block - PE
Tested at 2300 VAC (Rev. <E0 1500 VAC)
Protective circuit
External
See section "External fuses"
Internal
Snubber circuit (RC element) and varistor
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Table 348: X20DO2633 - Technical data
Summary of Contents for X20 System