Technical data • Individual components
80
Automation PC 3100 user's manual V0.60
3.5.8 5AC901.ISIO-00
3.5.8.1 General information
The ready relay function of IF option 5AC901.ISIO-00 can be controlled using the MTCX. Corresponding commands
must be issued by the MTCX in order to switch the ready relay.
In addition to the ready relay function, the reset button, power button and LED "Power" on the APC910/PPC900
or APC3100/PPC3100 can be made accessible externally.
Unlike IF option 5AC901.IRDY-00, ready relay 5AC901.ISIO-00 is not automatically switched on or off if the power
supply to the PC is switched on or off.
The maximum cable length for connecting the reset button, power button and LED "Power" is 2 m.
•
Connections for the reset button and power buttons on the PC
•
Connection for LED "Power" on the PC
•
1 normally closed contact, 1 normally open contact of the ready relay
•
Control of the ready relay functions using MTCX commands
•
Compatible with the APC910/PPC900 and APC3100/PPC3100
3.5.8.2 Order data
Model number
Short description
Figure
Interface options
5AC901.ISIO-00
Interface card - System I/O - For APC910/PPC900/APC3100/
PPC3100
Table 98: 5AC901.ISIO-00 - Order data
3.5.8.3 Technical data
Information:
The following specifications, properties and limit values apply only to this accessory and may deviate
from those that apply to the complete system. For the complete system in which this accessory is
installed, for example, the data specified for that complete system applies.
Model number
5AC901.ISIO-00
General information
B&R ID code
0xE674
Ready relay
Normally open contact and normally closed contact, max. 30 VDC, max. 1 A
Certifications
CE
Yes
UL
cULus E115267
Industrial control equipment
Electrical characteristics
Power consumption
0.5 W
Operating conditions
Pollution degree per EN 61131-2
Pollution degree 2
Environmental conditions
Temperature
Operation
0 to 55°C
1)
Storage
-20 to 60°C
Transport
-20 to 60°C
Table 99: 5AC901.ISIO-00 - Technical data