The AVC1 is an external voltage regulator/rec

Ɵ

fi

er 

designed for use with single-phase permanent-magnet 
alternators up to 20A in size.  Over-voltage protec

Ɵ

on, 

Charging System-fault and Low-voltage warning 
output, and 

fi

eld-adjustable charging voltage are 

integrated into the AVC1 control package.  
 
 
 
 

 
 

 

Case

 - Ground     

VOLT ADJ 

- Voltage Regula

Ɵ

on Adjustment 

CONFIG

 - LV Warning Con

fi

gura

Ɵ

on  

Terminals 1 & 2 

- AC Input   

 

 

Terminal 5 

- Warning Output 

Terminals 3 & 4 

- DC Output (+)   

  

Terminal 6 

- Control Input 

 

♦ 

For Duca

Ɵ

 retro

fi

t, AVC1 may be installed with no 

wiring changes. Otherwise, refer to Diagrams 1 & 2 
(reverse) for suggested wiring con

fi

gura

Ɵ

ons. 

♦ 

Disconnect ship’s ba

Ʃ

ery, Nega

Ɵ

ve (-) post 

fi

rst. 

♦ 

Mount the AVC1 & 

fi

lter capacitor (if used) on the 

fi

rewall or selected loca

Ɵ

on, terminal strip DOWN. 

♦ 

Wire the AC input.

 Connect Terminals 1 & 2 to the 

two AC leads from the alternator/dynamo, using 
the supplied wire terminals and heatshrink, if 
needed.  Note: there is no polarity in these wires. 

♦ 

Wire the DC power (+) output. 

Connect Terminals 

3 & 4 to the posi

Ɵ

ve (+) post on the 

fi

lter capacitor 

(if used) and the aircra

Ō

 bus at the output current 

limiter(s) or panel circuit breaker. 

Download the full AVC1 Technical Manual 

for more detailed installation guidance: 

www.BandC.com/AVC1install 

M

ONDAY

-F

RIDAY

 9:00 - 4:30 C

ENTRAL

 

 

The AVC1 provides warning output for Charging-
System Fault (CSF) and Low-Voltage (LV) condi

Ɵ

ons.  

LV warning is user-selected to trigger at one of three 
voltage thresholds. It may be disabled, also, if desired. 
 
 

 

LV warning op

Ɵ

ons may be selected by 

posi

Ɵ

oning two small 

DIP switches behind 
the machine screw 
cap labeled “CONFIG” 
on the side of the 
AVC1 enclosure.  The 
factory preset is 12.7v.   

LV Warning

 

Switch 1  Switch 2

 

Disabled DOWN 

DOWN 

12.7v DOWN 

UP 

13.0v UP 

DOWN 

13.3v UP 

UP 

LV warning-select DIP switches 

 

♦ 

Wire the Warning Output.

 Connect Terminal  5 to 

appropriate EFIS input or the panel indicator light. 

♦ 

Wire the Control Circuit. 

Connect Terminal 6 to the 

ba

Ʃ

ery/alternator master switch. 

♦ 

Wire the Ground circuit. 

Using 12AWG M22759/16 

wire, connect one of the two moun

Ɵ

ng 

fl

anges on 

the AVC1 to the aircra

Ō

 

fi

rewall Ground, Grounding 

block, or ba

Ʃ

ery Nega

Ɵ

ve (-) post.  

♦ 

Connect ship’s ba

Ʃ

ery, Posi

Ɵ

ve (+) post 

fi

rst. 

♦ 

Test the installa

Ɵ

on. Perform a normal engine start. 

Charging should be indicated at 13.8v to 14.4v. LV 
indica

Ɵ

on may occur ini

Ɵ

ally, but should cease as 

bus voltage rises above the selected warning 
threshold.

 