B&B Electronics VFG9000-SERIAL Quick Start Manual Download Page 1

  

CONFIGURED USING VLINX FIELDBUS GATEWAY MANAGER

  

ISOLATED RS232 AND RS485 MULTIPLEXED PORTS CAPABLE 

OF COMMUNICATING WITH RS232, RS422, RS485 AND DH485 

DEVICES AT UP TO 115,200 BAUD

  

EASY INSTALLATION

GENERAL DESCRIPTION

The  Vlinx  Fieldbus  Gateway  contains  a  proprietary  expansion  port  which 

provides a high speed, parallel architecture that extends the functionality and 

flexibility  of  the  platform.  This  approach  allows  these  products  to  evolve 

concurrently with the latest advances in communications and standards, without 

sacrificing performance. This high bandwidth channel has significantly greater 

throughput when compared to the traditional (external) serial gateway approach.

The VFG9000-SERIAL option card adds an additional RS232 and RS422/485 

port to the series. This isolated card protects user equipment from potentially 

harmful ground loops while providing high-speed RS232, RS422, RS485, and 

DH485 communication options to the end user.

The VFG9000-SERIAL communication card is easily installed by removing 

the  blank  expansion  port  cover  of  your  Fieldbus  Gateway,  and  plugging  the 

VFG9000-SERIAL card into the expansion port. Configuration is simple using 

B&B Electronics’ free Fieldbus Gateway Manager software.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the 

literature or on equipment must be observed to ensure personal safety and to 

prevent  damage  to  either  the  instrument  or  equipment  connected  to  it.  If 

equipment is used in a manner not specified by the manufacturer, the protection 

provided by the equipment may be impaired.

Do  not  use  the  controller  to  directly  command  motors,  valves,  or  other 

actuators not equipped with safeguards. To do so can be potentially harmful to 

persons or equipment in the event of a fault to the controller.

CONTENTS OF PACKAGE

- VFG9000-SERIAL option card

- This hardware bulletin

SPECIFICATIONS

1. 

POWER REQUIREMENTS:

 24 V @ 50 mA max. Power is supplied to the 

option card from the main board of the Fieldbus Gateway.

2. 

COMMUNICATIONS:

Serial Ports

: Format and Baud Rates for each port are individually software 

programmable up to 115,200 baud and are isolated to help prevent ground 

loops. The  RS422/485  and  DH485  port  via  RJ45  and  the  RS232  port  via 

RJ12  share  the  same  hardware.  The  VFG9000-SERIAL  option  card 

multiplexes the ports to communicate via two protocols. These ports may be 

used to configure different master protocols, but only one port may be used 

if configuring a slave protocol or AB DH485.

DH485 TXEN:

 Transmit enable; open collector, V

OH

 = 15 VDC, V

OL

 = 0.5 VDC

Isolation from VFG9000-SERIAL Communication ports to the Fieldbus 

Gateway:

  1000 VDC for 1 minute.

3. 

CERTIFICATIONS AND COMPLIANCES:

Refer  to  main  unit  manual  or  “Agency  Approvals”  section  of  B&B 

Electronics’ website for agency certifications.

ELECTROMAGNETIC COMPATIBILITY

Emissions and Immunity to EN 61326: Electrical Equipment for Measurement, 

Control and Laboratory use.

Reference Fieldbus Gateway unit for EMC specifications

4. 

ENVIRONMENTAL CONDITIONS

:

Refer to the specifications of the Fieldbus Gateway you are installing this 

card in.

5. 

CONSTRUCTION:

 For indoor use only. Installation Category II, Pollution 

Degree 2.

6. 

INSTALLATION  REQUIREMENTS:

  See  “Installing  the  VFG9000-

SERIAL Option card” for more details.

7. 

WEIGHT

: 1.9 oz (53.9 g)

ORDERING INFORMATION

DESCRIPTION

PART NUMBER

RS232/485 serial option card for Fieldbus Gateway

VFG9000-SERIAL

RS232/485 SERIAL OPTION CARD FOR VLINX FIELDBUS GATEWAY

VFG9000-SERIAL-

1012

qsg 

CAUTION: Risk of Danger.

Read complete instructions prior to  

installation and operation of the unit.

1

Phone: (815) 433-5100
Fax: (815) 4334-5104
www.bb-elec.com

LP0838X
Effective  01/10

WARNING - EXPLOSION HAZARD - SUBSTITUTION OF 

COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, 

DIVISION 2

THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I, 

DIVISION 2, GROUPS A, B, C, D, OR NON-HAZARDOUS 

LOCATIONS ONLY