13 / 30
0006081265_201212
EK
ENGLISH
LME CONTROL EQUIPMENT FOR BURNERS BPM 90 EVO ÷ 350 EVO
Operation, indications, diagnostics
The reset button «EK...» is the main element to access
all diagnostics functions (activation and deactivation), and
serves to unlock the command and control device.
The multicoloured «LED» indicates the command and con-
trol device status during both operation and diagnostic func-
tion.
RED
YELLOW
GREEN
Both «LED» and «EK...» are positioned under the transparent button. Pressing this button you reset the command and control
device.
Possibility of two diagnostic functions:
1. Visual indication directly on the reset button: operation and diagnostic of device status.
2. Diagnostics with interface: in this case the OCI400 connecting cable is necessary and it can be connected to a PC with ACS400
software, or to gas analysers of different manufacturers (see technical sheet 7614).
Visual indication:
During operation the command and control device phase is indicated on the reset button. The following table lists all colour sequences
and their meaning. To activate the diagnostic function hold the reset button down for at least 3 seconds. A quick red flashing indicates
that the function is active (see data sheet 7614). Likewise, hold the reset button down for at least 3 seconds to deactivate the function
(the switching will be indicated with a flashing yellow light).
Command and control device status indication
Condition
Colour sequence
Colours
Waiting conditions TW, other intermediate statuses
. . . . . . . . . . . . . . . .
No light
Ignition phase
Intermittent yellow
Correct operation, current strength of flame detector above the
minimum allowed
Green
Incorrect operation, current strength of flame detector below the
minimum allowed
Intermittent green
Decrease in power supply voltage
Alternating Yellow and Red
Burner in lock condition
Red
Fault indication (see colour legend)
Intermittent red
Extraneous light upon burner start-up
Alternating Green and Red
Quick flashing for diagnostics
Quick flashing red
Operating
position
Operating
position
Diagnostic
PC interface/diagnostic
analyser
Colour code table
No light
Red
Yellow
Green
Summary of Contents for BPM 90 EVO
Page 2: ......
Page 27: ...27 30 0006081265_201212 ITALIANO SCHEMI ELETTRICI...
Page 29: ...29 30 0006081265_201212 ITALIANO...
Page 48: ...20 30 0006081265_201212 ENGLISH...
Page 55: ...27 30 0006081265_201212 ENGLISH WIRING DIAGRAMS...
Page 57: ...29 30 0006081265_201212 ENGLISH...
Page 83: ...27 30 0006081265_201212 DEUTSCH SCHALTPLAN...
Page 85: ...29 30 0006081265_201212 DEUTSCH...
Page 111: ...27 30 0006081265_201212 P O L S K I SCHEMATY ELEKTRYCZNE...
Page 113: ...29 30 0006081265_201212 P O L S K I...
Page 115: ......