DESIGN CHARACTERISTICS
Burner with low NOx and CO/O2 emissions in accordance with
European standard EN676
•
Low NOx and internal recirculation combustion head with stainless
steel nozzle.
•
Mounting flange to the sliding generator, to adapt the protuberance
of the head to various types of heating generators.
•
Control panel complete with operation mimic panel and indicator
lights.
•
Automatic burner command and control equipment with
microprocessor in compliance with European standard EN298
integrated with valve seal control.
•
Display showing the operating sequence and error code in the event
of a lockout.
•
Flame detection by means of ionisation electrode.
• Flame inspection glass.
• Three-phase electric motor to run fan.
• Main gas train in EC version consisting of an operating and safety
valve with electro-magnetic operation, valve seal control, minimum
and maximum pressure switch, pressure regulator and gas filter.
•
Intelligent connection between boiler and gas train (fail safe).
¹) NATURAL GAS EMISSIONS
Classes defined according to EN 676 standards.
Class
NOx emissions in mg/kWh natural gas
1
≤ 170
2
≤ 120
3
≤ 80
4
≤ 60
Propane / natural gas CO emissions ≤ 100 mg/kWh
TECHNICAL FUNCTIONAL CHARACTERISTICS
•
Operation at two progressive stages / modulating.
•
Ability to operate with output modulation by means of automatic
regulator mounted on the control panel (to be ordered separately
with the modulation kit).
•
Fuel / combustion air flow rate regulation by means of two
servomotors controlled by the electronic equipment.
•
7-pole connectors for the auxiliary power supply and thermostat
connection, 4-pole connector for connecting the power electronic
regulator.
•
High fan output, low electrical input, low noise.
•
Modulation ratio ≥1:5.
•
Hinge opening on both sides for easy access to the combustion
head when burner is installed.
•
Air minimum and maximum flow rate regulation by means of electric
stepper servomotor with pause closure of damper to prevent any
heat dispersion to flue.
•
Electrical system with protection rating IP40.IP20.
•
Possibility of mounting the gas ramp in up or down position compared
to the head group.
²) PROPANE GAS EMISSIONS
Propane / natural gas CO emissions ≤ 100 mg/kWh
Class
NOx emissions in mg/kWh propane gas
1
≤ 230
2
≤ 180
3
≤ 140
4
≤ 110
²) PROPANE GAS EMISSIONS
Classes defined according to EN 676 standards.
Class
NOx emissions in mg/kWh propane gas
1
≤ 230
2
≤ 180
3
≤ 140
4
≤ 110
12 / 34
0006081328_202202
ENGLISH
Summary of Contents for 17530020
Page 2: ......
Page 32: ...SCHEMI ELETTRICI TBG 80 360LX ME TBG 80 360 ME 30 34 0006081328_202202 ITALIANO...
Page 33: ...TBG 80 360LX ME TBG 80 360 ME 31 34 0006081328_202202 ITALIANO...
Page 34: ...TBG 80 360LX ME TBG 80 360 ME I1 I2 BA I4 I3 32 34 0006081328_202202 ITALIANO...
Page 36: ...34 34 0006081328_202202 ITALIANO...
Page 66: ...WIRING DIAGRAMS TBG 80 360LX ME TBG 80 360 ME 30 34 0006081328_202202 ENGLISH...
Page 67: ...TBG 80 360LX ME TBG 80 360 ME 31 34 0006081328_202202 ENGLISH...
Page 68: ...TBG 80 360LX ME TBG 80 360 ME I1 I2 BA I4 I3 32 34 0006081328_202202 ENGLISH...
Page 70: ...34 34 0006081328_202202 ENGLISH...
Page 71: ......