8
english
5.1
Installation
For dimensions, see Fig. 4-1 on page 7.
CAUTION
Red light
If you look into the light beam, temporary blinding and
irritation of the eyes is possible.
Use of Controls or adjustment or performance of
procedures other than those specified herein may result
in hazardous radiation exposure.
►
Locate the sensor so that it is not possible to look
into the light beam even during operation.
►
Observe the instructions in this manual.
The through-beam sensor can be installed with two M3
screws on the side or with M18 nuts on an angle bracket
or panel.
5
Installation and connection
5.2
Electrical connection
Fig. 5-1:
4
3
1
2
Plug layout (top view of M12 plug on BOS)
Pin Signal
1 L+ (Operating v, SIO 10…30 V,
IO-Link 18…30 V)
2
I/Q (Digital input / digital output / analog output)
3 L− (Operating voltage −)
4
C/Q (IO-Link communication / digital output in SIO
mode)
Tab. 5-1: Pin assignment
Factory setting
– Mode: SIO mode
– Object recognition operating mode: Standard
– PIN 2: Push-pull switching output
– PIN 4: Push-pull switching output
Also see document
IO-Link configuration
under
www.balluff.com
on the product page.
5.3
Shielding and cable routing
Cable length
For IO-Link operation, the maximum cable length is 20 m.
BOS R080K-XM-RS10-(…-)S4 / BOS R080K-UIM-RE10-(…-)S4
Photoelectric Sensors
Summary of Contents for IO-Link BOS R080K-XM-RS10 S4 Series
Page 2: ...www balluff com ...
Page 4: ...www balluff com ...
Page 16: ......
Page 18: ...www balluff com ...
Page 30: ......
Page 32: ...www balluff com ...
Page 44: ......
Page 46: ...www balluff com ...
Page 58: ......
Page 60: ...www balluff com ...