www.balluff.com
9
english
5.1
Assembling the amplifier
The following fitting methods are available:
– Simple clamp fitting on the hat rail acc. to DIN, 35 mm
or 15 mm
– Screw fixing with pan-head M3 screws
5.2
Connecting the amplifier
The amplifier can be operated with type
BCS…-XXS-…
sensors.
Fig. 5-1: Connecting the sensor
5.3
Electrical Connection
Fig. 5-2:
4
3
1
2
Plug layout (top view of M12 plug)
Pin Color
Signal
1 BN
L+ (Operating v, SIO 10…30 V,
IO-Link 18…30 V)
2
WH
Teach line
3 BU
L− (Operating voltage −)
4
BK
C/Q output signal
Tab. 5-1: Pin assignment
Teach-in mode is only useful in SIO mode.
In normal operation, the white teach line must
always be connected to the blue negative line.
5
Installation and connection
5.4
SIO mode
Fig. 5-3:
BN
+
OUT
ext. prog.
–
3
+
–
BK
BU
WH
PNP
1
4
2
3
+
–
BN
3
BK
BU
WH
NPN
1
4
3
2
+
OUT
ext. prog.
–
SIO mode (PNP/NPN)
5.5
IO-Link operation
Fig. 5-4:
BN
+
OUT
ext. prog.
–
+
C/Q
Master
–
3
BK
BU
WH
1
4
2
3
IO-Link operation
BAE SA-CS-027-YI-BP00,3 GS04
IO-Link Sensor Amplifier
Summary of Contents for IO-Link BAE SA-CS-027-YI-BP00,3 GS04
Page 1: ...BAE SA CS 027 YI BP00 3 GS04 deutsch Betriebsanleitung english User s guide ...
Page 2: ...www balluff com ...
Page 3: ...BAE SA CS 027 YI BP00 3 GS04 Betriebsanleitung deutsch ...
Page 4: ...www balluff com ...
Page 26: ......
Page 27: ...BAE SA CS 027 YI BP00 3 GS04 User s Guide english ...
Page 28: ...www balluff com ...