Adjusting (continued)
Displayed values (example)
At 0…10 V
At 4…20 mA
Set end point
►
Bring magnet to the new end point.
9.89 V
19.13 mA
►
Activate
b
for at least 2 s.
> 2 s
b
⇒
The new end point is set with the last valid end
value.
10.00 V
20.00 mA
Adjust end value
►
The end value can be changed using
a
and
b
. The
gradient of the curve changes (see page 15).
10.00 V
20.00 mA
8.00 V
16.80 mA
►
End calibration procedure: Briefly press
a
and
b
simultaneously (< 1 s).
⇒
Set position value is saved.
< 1 s
a
b
2.00 V
6.00 mA
8.00 V
16.80 mA
End adjustment
►
Briefly activate
a
and
b
simultaneously (< 1 s).
< 1 s
a
b
10.50 V
3.60 mA
⇒
The current position value is displayed once the
buttons are released.
7.63 V
18.56 mA
Any of the individual steps for settings can be
selected. The adjustment process can be
ended at any time.
BTL7-A/C/E/G5 _ _ -M _ _ _ _ -K(8)-SR32/SR115/_ _ _
Magnetostrictive Linear Position Sensor – Rod Style
Summary of Contents for BTL7-A510 Series
Page 2: ...www balluff com...
Page 3: ...Betriebsanleitung deutsch BTL7 A C E G5_ _ M_ _ _ _ K 8 SR32 SR115 _ _ _...
Page 4: ...www balluff com...
Page 29: ...User s Guide english BTL7 A C E G5_ _ M_ _ _ _ K 8 SR32 SR115 _ _ _...
Page 30: ...www balluff com...
Page 55: ...Notice d utilisation fran ais BTL7 A C E G5_ _ M_ _ _ _ K 8 SR32 SR115 _ _ _...
Page 56: ...www balluff com...
Page 81: ...Manuale d uso italiano BTL7 A C E G5_ _ M_ _ _ _ K 8 SR32 SR115 _ _ _...
Page 82: ...www balluff com...
Page 107: ...Manual de instrucciones espa ol BTL7 A C E G5_ _ M_ _ _ _ K 8 SR32 SR115 _ _ _...
Page 108: ...www balluff com...
Page 133: ......