65
english
5
Secondary Device Functions (continued)
5.10 Extreme Environment Status
5.10.1 Description
With the help of the
Extreme Environment Status
, the time
is recorded in which the device was exposed to extreme
conditions. In parameter
Lifetime Extreme Thresholds
, limit
values can be configured for the respective conditions.
Parameter
Lifetime Extreme Status
can be used to read
out the current status as well as the summed time.
5.10.2 Mathematics/Algorithm
If one (or more) extreme conditions are met, the device
begins to record the time.
If the power supply is interrupted during this time,
the time counter can have an error of maximum
180 seconds.
5.10.3 Process Data
Object ID
Name
Description
Direction
0x0041 (65)
Lifetime Extreme
One or more extreme conditions present.
Input
0x0042 (66)
Lifetime Extreme Time
Summed time in which the device was exposed to an extreme
condition.
Input
Tab. 5-47: Extreme environment status – Process data
5.10.4 ISDU
Name
Index
Subindex
Access
Length
Data Type
Data
Storage
Default
Lifetime
Extreme
Thresholds
0x00D0 (208)
0
R/W
8 bytes
Yes
Threshold
Vibration
1
R/W
4 bytes
FLOAT
No
1770
Upper
Threshold
Temperature
2
R/W
2 bytes
INT16
No
0x0055 (85)
Lower
Threshold
Temperature
3
R/W
2 bytes
INT16
No
0xFFF6 (−10)
Lifetime
Extreme
Status
0x00D1 (209)
0
R
5 bytes
No
State
1
R
1 byte
ENUM
No
Time
2
R
4 bytes
UINT32
No
Tab. 5-48: Extreme environment status – ISDU
For the internal humidity, it is not possible to
parameterize your own limit values.
BOS R254K-UUI-LH10-S4
Photoelectric Sensors
Summary of Contents for BOS R254K-UUI-LH10-S4
Page 1: ...deutsch IO Link Konfiguration english IO Link Configuration BOS R254K UUI LH10 S4...
Page 2: ...www balluff com...
Page 3: ...BOS R254K UUI LH10 S4 IO Link Konfiguration deutsch...
Page 4: ...www balluff com...
Page 99: ...BOS R254K UUI LH10 S4 IO Link Configuration english...
Page 100: ...www balluff com...
Page 195: ......