Beginning Edge Setup Procedure for the BOL 27K-PS/NS-01-S115 

Optical Line Sensor 

 

Setting up the sensor 
 

Note

:

 

Assuming factory defaults upon setup.  To reset the sensor, enter 

the MENU (step 4 below) and press the + button until RESET (rESE) is 
displayed.  Press the SET button. 

1)

 

Place a 150mm strip of reflective tape (BOL 27K-TAPE-01) on a flat surface 

90˚ to the face of the sensor. 

2)

 

Maximum sensing height is 200mm.  Measurement range on tape is 150mm at 
this distance.  (Note: at closer distances, the analog scale will be less). 

3)

 

Once the sensor is mounted, press and hold the 

+

 and 

 buttons 

simultaneously for a minimum of 6 sec. until 

TAPE

 flashes.  (The area of the 

tape has been taught and the 4-20mA scale has been designated). 

4)

 

Press the 

SET

 button for a minimum of 6 sec.  

MENU

 will display on the 

screen.   

5)

 

Press the 

+

 button until 

SAVE 

is displayed.   

6)

 

Press the 

SET

 button to save the beginning edge mode. 

 

Note: 

The sensor will automatically default to a ready state if a button has not been 

pushed within 8 seconds while programming.  If a mistake is made upon setup, wait a 
minimum of 8 sec for the sensor to exit the programming mode and reset to factory 
defaults.   
 

Note: 

The measured object does not have to completely remain within the measureable 

window on the tape during area measurement mode.  Edges of material can extend 
beyond range of sensor.

   

 
Setting Tolerances for Discrete Output 

The discrete output can be triggered to turn on between two values.

 

 

1)

 

Place the material under the sensor to determine where the desired tolerance 
levels will be set (referencing the value displayed on the sensor screen for 
high and low values).   

2)

 

Press the 

button for a minimum of 2 sec.  

Th_1 

will be displayed.   

3)

 

Press the 

SET 

button.   

4)

 

Press the 

or 

– 

button to increment/decrement the value where the discrete 

output setting is desired to 

turn on

.   

5)

 

Hold the 

SET 

button for a minimum of 1 sec to save the low-end point. 

6)

 

Repeat steps 2-5 and select 

Th_2

 in this procedure to teach the high-end point 

where the discrete output will 

turn off