8
english
4.3
Display elements
Fig. 4-3:
0
1
2
3
IP
SN
GW
BNI XXX-XXX-XXX-XXX
BNIXXXX
MAC-ID
POWER
OUT
IN
LK2
LK1
00-19-31-XX-XX-XX
4
0
15
14
07
06
13
12
05
04
11
10
03
02
09
08
01
00
MOD NET
US
LK2
100
LK1
100
UA
1
5
2
6
3
7
S
P
Status LEDs
Port/Pin LEDs:
Status of IO-Link and
I/O-Ports
Display elements
Port/Pin LEDs
LED number
Assignment
Even
Pin 4
Odd
Pin 2
Tab. 4-1: Port/Pin LEDs
Port/Pin LEDs Standard Port
Signal
Meaning
Off
State of input or output pins is 0
Yellow, static State of input or output pins is 1
Both LEDs
flashing red
Short circuit of sensor supply between
pin 1 and pin 3
Red, static
Short circuit at output on pin 2/4 against
pin 3
Red, static
No high signal at diagnostic input
Red, static
24 V input signal on configured output
(actuator warning)
Tab. 4-2: LEDs Standard Port
Port/Pin LEDs IO-Link Port
Signal
Meaning
Green, static IO-Link connection active
Flashing
green
No IO-Link connection or incorrect
IO-Link device
Green, fast
flashing
IO-Link: Preoperate during data storage
Red, fast
flashing
Validation failed / incorrect configuration
of the IO-Link data length
Red, fast
flashing
Data storage failed / incorrect device for
data storage
Red, static
IO-Link: Short circuit of pin 4 against
pin 3
Tab. 4-3: LEDs IO-Link Port
Status LEDs
LED Signal
Meaning
US
Green, static Input voltage OK
Red flashing
Input voltage low (< 18 V)
UA
Green, static Output voltage OK
Red flashing
Output voltage low (< 18 V)
Red, static
No output voltage present
(< 11 V)
MOD Flashing
green
Incorrect or no module
configuration
Green, static Module working
Red flashing
Fixed bus cycle not possible
Red/Green
flashing
Starting sequence
NET
Off
Module has no IP address
Flashing
green
Module has an IP address, but no
connection established
Green, static Connection is established
Red flashing
Connection timeout
Red/Green
flashing
Starting sequence
100
Off
Transmission rate: 10 Mbit/s
Yellow, static Transmission rate: 100 Mbit/s
LK1/2 Flashing
green
Data transfer
Tab. 4-4: Status LEDs
4.4
Labeling
Fig. 4-4:
0
1
2
3
IP
SN
GW
BNI XXX-XXX-XXX-XXX
BNIXXXX
MAC-ID
POWER
OUT
IN
LK2
LK1
00-19-31-XX-XX-XX
4
0
15
14
07
06
13
12
05
04
11
10
03
02
09
08
01
00
MOD NET
US
LK2
100
LK1
100
UA
1
5
2
6
3
7
S
P
Order code
Type
Labeling (example)
4
Product description (continued)
BNI EIP-508-105-Z067
Network interface
Summary of Contents for BNI00H7
Page 1: ...deutsch Betriebsanleitung english User s guide BNI EIP 508 105 Z067...
Page 2: ...www balluff com...
Page 3: ...BNI EIP 508 105 Z067 Betriebsanleitung deutsch...
Page 4: ...www balluff com...
Page 17: ...BNI EIP 508 105 Z067 User s Guide english...
Page 18: ...www balluff com...
Page 31: ......