BNI PBS-506-001-Z011
BNI PBS-507-001-Z011
IP67 Module, Profibus IO-Link Master
User´s Guide
Page 1: ...BNI PBS 506 001 Z011 BNI PBS 507 001 Z011 IP67 Module Profibus IO Link Master User s Guide...
Page 2: ...ion mode 8 Standard IO modes SIO mode 8 5 Technical Data 9 5 1 Dimensions 9 5 2 Mechanical Data 9 5 3 Electrical Data 9 5 4 IO Link data 9 5 5 Operating conditions 9 6 Installation 10 6 1 Mechanical c...
Page 3: ...ut 26 8 2 Diagnostics telegram 27 8 3 Norm diagnostics 27 Norm diagnostics coding 27 Status 1 27 Status 2 28 Status 3 28 Address 28 Ident_Number_High_Byte 28 Ident_Number_Low_Byte 28 8 4 Device specif...
Page 4: ...shown without additional indicators e g 123 Hexadecimal numbers are shown with the additional indicator hex e g 00hex Menu commands Menu commands are separated by a vertical line Tools Install new GS...
Page 5: ...approved power supply see section 4 Technical data Only approved cable may be used Material resistance The BNI PBS has good chemical and oil resistance If aggressive media are used the material resist...
Page 6: ...506 001 Z011 1 Ground connection 2 M12 Profibus IN 3 Address switches 4 Supply POWER 5 I O port 0 6 I O port 1 7 IO Link port 2 8 IO Link port 3 9 I O IO Link port LED 10 Status LED communication mod...
Page 7: ...NI PBS 507 001 Z011 1 Ground connection 2 M12 Profibus IN 3 Address switches 4 Supply POWER 5 I O IO Link port 0 6 I O IO Link port 1 7 I O IO Link port 2 8 I O IO Link port 3 9 I O IO Link port LED 1...
Page 8: ...municate over this bus system Variants Profibus DP for fast cyclical data exchange with field Devices Profibus PA for applications in process automation in the intrinsically safe area Profibus FMS for...
Page 9: ...sor map Inputs 1 byte 32 bytes Outputs 1 byte 32 bytes Or combined input output modules Deterministic time behavior Typically 3 ms cycle time 16 bits of process data and 38 4 Kbaud transmission rate S...
Page 10: ...male Enclosure rating IP67 only when plugged in and threaded in Weight ca 352 g 5 3 Electrical Data Operating voltage 18 30 V DC Ripple 1 Current draw without load 200 mA 5 4 IO Link data Baud rate CO...
Page 11: ...6 screws and 2 washers Keep a distance of at least 3 mm between two modules Note Tip Recommended drilling distance 210 5 0 2 mm by using M6 Screws With these drilling distance all IP67 Profibus Profin...
Page 12: ...ybrid cable is not allowed Power 7 8 5pol male Pin Function 1 Ground 0V 2 Ground 0V 3 Function ground FE 4 Module and Sensor supply 24V 5 Actuator supply 24V 24 V DC Provide sensor bus power and actua...
Page 13: ...e terminated with a bus terminator The termination resistor requires no external voltage Unused sockets must be fitted with cover caps to ensure IP 67 protection rating 6 4 Ports The sensor supply is...
Page 14: ...he GSD files are available in 2 languages for downloading over the Internet www balluff com The data modules of an IO Link module are represented in the project planning software by slot The GSD file...
Page 15: ...words Header special format Determining in outputs of the module 0 0 Empty 0 1 Ports are inputs 1 length byte for input data 1 0 Ports are outputs 1 length byte for output data 1 1 Ports may be in or...
Page 16: ...97hex 05hex IOL_O_32byte 32 Byte 81hex 9Fhex 05hex Data modules for IO Link inputs and outputs Data module Data width Coding Input Output IOL_I O 1 _1 byte 1 Byte 1 Byte C1hex80hex80hex05hex IOL_I O...
Page 17: ...ctuator shut down Pin 4 1 Byte 10hex Actuator shut down Pin 2 1 Byte 10hex Actuator warning Pin 4 1 Byte 10hex Actuator warning Pin 2 1 Byte 10hex Restart Pin 4 1 Byte 20hex Restart Pin 2 1 Byte 20hex...
Page 18: ...hdog access monitoring in the Device 4 Freeze_req Operate DP Device in freeze mode 5 Sync_req Operate DP Device in sync mode 6 Lock_req see below for coding 7 Unlock_req Coding of lock and unlock Lock...
Page 19: ...5 4 3 2 1 0 0 11 255 0x00 0x0B 0xFF Ident_Number _High Ident_Number_High Identnummer High Byte Byte 1 7 6 5 4 3 2 1 0 0 255 0x00 0xFF Ident_Number _Low Ident_Number_Low Identnummer Low Byte Byte 1 7 6...
Page 20: ...10 Global settings for a standard I O port Decimal Binary Meaning 08 00001000 Digital input NO 09 00001001 Digital input NC 10 00001010 Digital output 11 00001011 Diagnostic input IO Link Port Configu...
Page 21: ...t_2 3 MinTSDR 4 Indent_Number_High 5 Indent_Number_Low 6 Group_Intend 7 0x80 DPV1 Status 1 DPV1 parameters 8 0x00 DPV1 Status 2 9 0x00 DPV1 Status 3 10 0x0F Global diagnostic Channel related diagnosti...
Page 22: ...20 0x00 Parameter Server Conflict Resolution Download Enable Upload Enable 21 0x10 Module Identifier Validation type IO Link module 16 byte IN 16 byte Out 22 0x00 Cycle Time 23 0x00 Process data offse...
Page 23: ...or supply Low voltage actuator supply Head modules 11 0x00 Function Port 0 3 Pin 4 12 0x44 Function Port 4 5 Pin 4 13 0x44 Function Port 6 7 Pin 4 14 0x00 Function Port 0 3 Pin 2 15 0x00 Function Port...
Page 24: ...on the PC the GSD file for the module must be installed Open a new project Open hardware configurator Select menu command Tools Install new GSD The window Install new GSD opens Select directory and G...
Page 25: ...com 24 7 Startup Requirements For the integration of a Profibus Device a configuration at the PLC and the DP interface is required Integration of the module Select the Profibus Device from the catalo...
Page 26: ...dialogue Properties DP slave appears The function of the single pins can be defined Slot configuration When the IO Link interface is activated in the slots 2 5 the corresponding IO Link module has to...
Page 27: ...h indicate the operating states LED 0 PIN 4 LED 1 PIN 2 Indicator Function IO Link Output Input Diagnostic Input Off Signal 0 Signal 0 Diagnostics 0 Yellow Signal 1 Signal 1 Red SC Imax I Output Imax...
Page 28: ...it to 1 if the DP Device cannot be reached 1 Station_not_ready The DP Device sets the bit to 1 if it is not yet ready for data exchange 2 Cfg_Fault The DP Device sets the bit to 1 if the configuratio...
Page 29: ...Deactivated The DP Device always sets the bit to 0 The DP Master sets it to 1 if the DP Device is removed from the Master parameter set Status 3 Byte 2 Status 3 Bit Meaning 0 6 reserved 7 Ext_Diag_Ov...
Page 30: ...r 00 Device specific diagnostics 0 5 Number of the bytes Status Typ Byte 1 Status Typ Bit Meaning 7 Status Block 6 2 Not used 1 Module status 0 Not used Slotnummer Byte 2 Slotnummer Bit Meaning 0 7 0...
Page 31: ...he module specific diagnostics 1 activated 0 deactivated Coding of the module specific Diagnostic Header Byte 0 Header Bit Meaning 6 7 Header 01 modulespecific diagnostic 0 5 Number of the bytes Modul...
Page 32: ...and Output 0 5 Number of affected channels in module 0 63 decimal Head module IO Link ports 00 Port 0 Pin 4 01 Port 1 Pin 4 02 Port 2 Pin 4 03 Port 3 Pin 4 04 Port 0 Pin 2 05 Port 1 Pin 2 06 Port 2 Pi...
Page 33: ...etwork Interface Profibus Functions 506 IP67 IO Module 2 x IO Link ports 507 IP67 IO Module 4 x IO Link ports Variants 001 Standard version Mechanical version Z011 Material Die cast zinc matt nickel p...
Page 34: ...l O SI 58 3A 101 65 e 16 10 Ctrl P DLE 59 3B 102 66 f 17 11 Ctrl Q DC1 60 3C 103 67 g 18 12 Ctrl R DC2 61 3D 104 68 h 19 13 Ctrl S DC3 62 3E 105 69 i 20 14 Ctrl T DC4 63 3F 106 6A j 21 15 Ctrl U NAK 6...
Page 35: ...www balluff com 34 10 Notes...
Page 36: ...www balluff com 35 10 Notes...
Page 37: ...www balluff com 36 www balluff com Balluff GmbH Schurwaldstrasse 9 73765 Neuhausen a d F Germany Tel 49 7158 173 0 Fax 49 7158 5010 balluff balluff de Nr 893775 E Edition 1212 Subject to modification...