5
Technical Data
5.1.
Dimensions
5.2.
Mechanical
Data
Housing material
Die-cast zinc housing
IO-Link-Port
M12, A-coded, male,
Analog Ports
M12, female, 5-poles
Enclosure rating per IEC 60529
IP67 (only when plugged in and threaded in)
Weight
ca. 500 g
Dimensions (W × H × D in mm)
68 x 181,5 x 31,8
5.3.
Electrical Data
Operating conditions
18 ... 30,2 V DC, per EN 61131-2
Ripple
< 1 %
Current draw without load
≤ 80 mA
Voltage input measuring error
<±0.1% full-scale, <2 mV, which is greater
Current input measuring error
<±0.1% full-scale, <4 uA, which is greater
Pt100, Pt1000 input measuring
error
<±0.2% full-scale, <0.2 °C, which is greater
TypJ thermocouple measuring
error
-100 °C -
+100 °C: <2.5˘C
+100 °C - +1200 °C: <2 °C
TypK thermocouple measuring
error
-180 °C - -
100 °C: <3˘C
-100 °C - +1370 °C: <2 °C
TypC thermocouple measuring
error
0…2300°C:<2,5°C
Temperature coefficient
<±0.01% / °C
5.4.
Operating
conditions
Ambient temperature
-
5 °C … +70 °C
Storage temperature
-
25 °C … +70 °C