Process data
4.1
Process data inputs
The input data have a size of 392 bytes. The table below
shows the assignment of the process data inputs.
Byte
Module part
Description
0…7
Standard I/O
ports
Process data inputs for the
standard inputs
8…55
IO-Link Port 0
Process data inputs for the
IO-Link Port 0
56…103
IO-Link Port 1
Process data inputs for the
IO-Link Port 1
104…151 IO-Link Port 2
Process data inputs for the
IO-Link Port 2
152…199 IO-Link Port 3
Process data inputs for the
IO-Link Port 3
200…247 IO-Link Port 4
Process data inputs for the
IO-Link Port 4
248…295 IO-Link Port 5
Process data inputs for the
IO-Link Port 5
296…343 IO-Link Port 6
Process data inputs for the
IO-Link Port 6
344…391 IO-Link Port 7
Process data inputs for the
IO-Link Port 7
Tab. 4-1: Process data inputs BNI EIP-508-105-Z067
4.1.1 Standard input data
Byte
Bit
Description
7
6
5
4
3
2
1
0
0
I32
I34
I22
I24
I12
I14
I02
I04
Input data
I04: Input for port 0, pin 4
The result is only 0 when the port is configured as an
IO-Link Port.
1
I72
I74
I62
I64
I52
I54
I42
I44
2
S3
S2
S1
S0
Short circuit status
Short circuit between pin 1 and 3 at reported port
3
S7
S6
S5
S4
4
O32
O34
O22
O24
O12
O14
O02
O04 Overload status
O04: Overload at port 0, pin 4
Only if the port is configured as an output.
5
O72
O74
O62
O64
O52
O54
O42
O44
6
0
0
0
0
0
NA
PS
PA
Status of power supply
NA: No actuator supply
PS: Power supply of sensor
PA: Power supply of actuator
7
0
0
0
0
0
0
0
0
reserved
Tab. 4-2: Standard input data
BNI EIP-508-105-Z067
Network interface
Summary of Contents for BNI EIP-508-105-Z067
Page 1: ...deutsch Konfigurationsanleitung english Configuration Guide BNI EIP 508 105 Z067 ...
Page 2: ...www balluff com ...
Page 3: ...BNI EIP 508 105 Z067 Konfigurationsanleitung deutsch ...
Page 4: ...www balluff com ...
Page 45: ...BNI EIP 508 105 Z067 Configuration Guide english ...
Page 46: ...www balluff com ...
Page 87: ......