
Industrial Ethernet (IND)
INTERFACE
79
5
The
OnDemand Status Page
will be displayed.
13. At the
OnDemand Status Page
, click the link labeled “
Main Page
” to return to the
HTTP Server
– Main Page
.
5.6 CONFIGURING PLC CONTROLLER TAGS
After you have configured the BIS M-
626’s Node via the
OnDemand Configuration Page
,
open your PLC program (i.e. RSLogix 5000) and, if you have not already done so, define two
Controller Tags
(a
Write Tag
and a
Read Tag
).
Controller Tag Naming
Controller Tags
need to be assigned a name and size. Be sure to use the same
Write Tag
Name
and
Read Tag Name
that you specified in the
OnDemand Node Configuration
(i.e.,
EMS_WRITE1 and EMS_READ1).
Controller Tag Size
Due to handshaking overhead,
Controller Tags
must have the size capacity to store an
integer array equal to your previously specified
Write/Read Size
+ three words
.
So for example, if the
Read Size
you specified earlier was 100 words, the corresponding
Read Tag
in the PLC must be able to store an array of 103 integers.
The
Write Tag
holds messages and response data generated by the BIS M-626 that
is bound for the host or PLC.
The
Read Tag
holds RFID commands and instructions intended for the BIS M-626.
Summary of Contents for BIS M-370-000-A02
Page 1: ......
Page 2: ......
Page 3: ......
Page 7: ......
Page 16: ...9 BIS M 371 000 A01 BIS M 372 000 A01 BIS M 373 000 A01 BIS M 370 000 A02 Figure G...
Page 17: ...10...
Page 21: ...BIS M 62_ MANUAL 14 1...
Page 60: ...INSTALLATION 53 2...
Page 77: ...BIS M 62_ MANUAL 70 4...
Page 101: ...BIS M 62_ MANUAL 94 5...
Page 103: ...BIS M 62_ MANUAL 96 6 The HTTP Server Main Page will be displayed...
Page 126: ...DEVICENET INTERFACE 119 8...
Page 185: ...BIS M 62_ MANUAL 178 10...
Page 188: ...RFID OPERATING PRINCIPLES 181 11...