MODBUS TCP INTERFACE
99
6
6.2.1 Modbus TCP - Command Packet Structure
Consume Registers hold data that is destined for the BIS M-626_. Modbus TCP commands
must be placed in the holding registers, starting at address 40001, of Device ID 01 (Node
Input Page 01). Commands utilize at least six registers (double-byte values or words).
Modbus
Address
(4xxxx / 3xxxx)
Read / Write
Privilege
Register Description
(40001) 1
R/W
2-byte Consume Data Overall Length
(> 0 indicates data is available; BIS M-626_
clears to 0 after data is processed)
2
R/W
MSB = Reader Type
LSB = Command ID
3
R/W
MSB = 0x00
LSB = Node ID (0x01 for the BIS M-626_)
4
R/W
2-byte Timeout Value
(0-65535) measured in milliseconds
5
R/W
2-byte Start Address
(0-65535)
6
R/W
2-byte Read/Block Size
(0-65535 bytes)
7
– 32774
R/W
BIS M-626_ Consume Data (when applicable)
32775
– 65536
R/W
Reserved
6.2.2 Modbus TCP - Response Packet Structure
Produce Registers
hold data that is destined for the host or PLC.
Modbus
Address
(4xxxx / 3xxxx)
Read / Write
Privilege
Register Description
(40001) 1
R/W
2-byte Produce Data Overall Length
(> 0 indicates data is available; Modbus Client
clears to 0 after data is processed)
2
RO
MSB = Reader Type
LSB = Command Echo
3
RO
Node ID Number (33 for the BIS M-626_)
4
RO
Timeout Value (0-65535)
5
RO
Read/Write Start Address (0-65535)
6
RO
Read/Block Size (0-65535 bytes)
7
– 32774
RO
BIS M-626_ Produce Data (when applicable)
32775
– 65536
RO
Reserved
Summary of Contents for BIS M-370-000-A02
Page 1: ......
Page 2: ......
Page 3: ......
Page 7: ......
Page 16: ...9 BIS M 371 000 A01 BIS M 372 000 A01 BIS M 373 000 A01 BIS M 370 000 A02 Figure G...
Page 17: ...10...
Page 21: ...BIS M 62_ MANUAL 14 1...
Page 60: ...INSTALLATION 53 2...
Page 77: ...BIS M 62_ MANUAL 70 4...
Page 101: ...BIS M 62_ MANUAL 94 5...
Page 103: ...BIS M 62_ MANUAL 96 6 The HTTP Server Main Page will be displayed...
Page 126: ...DEVICENET INTERFACE 119 8...
Page 185: ...BIS M 62_ MANUAL 178 10...
Page 188: ...RFID OPERATING PRINCIPLES 181 11...