Electrical connection
The device is designed, tested and approved for branch
circuits up to 20 A (UL) and 32 A (IEC) without an
additional protective device. If an external fuse is used, do
not use circuit breakers smaller than 6 A, B or C
characteristics to avoid false tripping. A disconnect device
must be provided for the input of the device. This must be
placed in a suitable location and be easily accessible. The
disconnect device must be marked as such for the device.
The negative potential of the outputs is permanently
connected to PE in the device. Do not connect the
negative potential of an output to PE outside the device.
Input X1
BAE PS-…-
609
-I
BAE PS-…-
611
-I
3
1
4
2
7/8" connector
M12 connector, S-coded
Fig. 5-3: Pin assignment input X1 (top view of connector on device)
Pin
Signal
1
L1
2
L2
3
L3
4 /
PE
Tab. 5-1: Pin assignment input X1
Connection X2 (IO-Link)
Fig. 5-4:
3
1
4
2
5
Pin assignment of connection X2 (IO-Link), M12 connector,
A-coded (top view of connector on device)
Pin
Signal
1
24 V DC
2
Not used
3
GND
4
C/Q (IO-Link communication)
5
Not used
Tab. 5-2: Pin assignment connection X2 (IO-Link)
Outputs X3 and X4
Fig. 5-5: BAE PS-…-
609
-I: Pin assignment of outputs X3 and X4,
7/8" socket (top view of socket on device)
Fig. 5-6: BAE PS-…-
611
-I: Pin assignment of outputs X3 and X4,
M12 socket, L-coded (top view of socket on device)
Pin
BAE PS-…-609-I
BAE PS-…-611-I
Signal Description
Signal
Description
1
GND
U
A
,
output 2/4
24 V DC
U
S
,
output 1/3
2
GND
U
S
,
output 1/3
GND
U
A
,
output 2/4
3
FE
GND
U
S
,
output 1/3
4
24 V DC
U
S
,
output 1/3
24 V DC
U
A
,
output 2/4
5
24 V DC
U
A
,
output 2/4
FE