MN715J
Programming and Operation 4-19
Parameter Block Definitions
Level 2 Continued
SECURITY CONTROL
Security State
Off - No security access code required to change parameter values.
Local Security - Requires security access code to be entered before changes
can be made using the Keypad.
Access Timeout
The time in seconds the security access remains enabled after
leaving the programming mode. If you exit and go back into the program mode
within this time limit, the security Access Code does not have to be re-entered.
This timer starts when leaving the program mode (by pressing DISP etc.).
Access Code
A 4 digit code. You must know this code to change secured Level 1
and Level 2 values.
Note: Please record your access code and store it in a safe place. If you cannot
gain entry into parameter values to change a protected parameter, please
contact Baldor. Be prepared to give the 5 digit code located on the lower right
side of the Keypad Display at the Enter Code prompt.
MOTOR DATA
Motor Rated Amps
The rated current of the motor (listed on the motor nameplate). If
the motor current exceeds this value for a period of time, an Overload fault will
occur. If multiple motors are used on one control, add the Motor Rated Amps for
all motors and enter this value.
Motor Rated Speed
The rated speed of the motor (listed on the motor nameplate). If
Motor Rated SPD = 1750 RPM and Motor Rated Freq = 60 Hz, the Keypad
Display will show 1750 RPM at 60 Hz and 875 RPM at 30Hz.
Motor Rated Freq
The rated frequency of the motor (listed on the motor nameplate).
BRAKE ADJUST
Resistor Ohms
The dynamic braking resistor value in ohms. Refer to Appendix A or
call Baldor for additional information. If dynamic braking is not installed, enter
zero.
Resistor Watts
The dynamic braking resistor watts rating. Refer to dynamic braking
manual or call Baldor for additional information. If dynamic braking is not
installed, enter zero.
DC Brake Voltage
The amount of DC braking voltage applied to the motor windings
during a stop command. Increase this value for more braking torque during
stops. The increased braking voltage may cause the motor to overheat for
applications that require frequent starts/stops. Be careful in selecting this value.
The maximum DC Brake Voltage = (1.414)X(Max Output Volts).
DC Brake FREQ
The output frequency (to the motor) at which DC injection braking
will begin during Decel.
Brake on Stop
If ON, DC injection braking will begin when a stop command is issued.
After a stop command, the DC brake voltage will be applied to the motor windings
when the output frequency reaches the DC brake frequency.
Brake on Reverse
If set to ON, DC injection braking will begin when the control is
commanded to drive the motor in the opposite direction. Braking continues until
the motor is stopped. The motor will then accelerate in the opposite direction.
Summary of Contents for ID15J101-ER
Page 1: ...Series 15J Inverter Control 7 04 MN715J Installation and Operating Manual ...
Page 5: ...iv Table of Contents MN715J ...
Page 11: ...2 4 General Information MN715J ...
Page 59: ...4 22 Programming and Operation MN715J ...
Page 75: ...6 6 Specifications and Product Data MN715J ...
Page 79: ...A 4 Dynamic Brake Hardware MN715J ...
Page 86: ...Appendix C Remote Keypad Mounting Template MN715J Remote Keypad Mounting Template C 1 ...