background image

Chapter 1. Modbus Communications 

22

Communications Options User’s Guide

1.5 Swapping the Floating Point

To represent a correct floating point value, you may need to swap the reading from two registers. Some applications 

allow you to swap the registers. Some do not.
When using the 

Modscan32

 utility in order to monitor register values, you need to select 

03: HOLDING REGISTER

 (see 

Figure 3), select the corresponding communications parameters in the menu item 

Connection-Connect

, and hit 

OK

 to 

make a connection.

Figure 3: Selecting the Holding Register

Select

Summary of Contents for Panametrics XMT686i

Page 1: ...panametrics com Flow 916 115 F JUL 2021 Communications Options User s Guide...

Page 2: ......

Page 3: ...material contains one or more registered trademarks of Baker Hughes Company and its subsidiaries in one or more countries All third party product and company names are trademarks of their respective h...

Page 4: ...ii no content intended for this page...

Page 5: ...the Assigned IP Address 35 3 2 5 Changing IP Parameters 36 3 2 6 Changing Modbus TCP Network Parameters 36 3 2 7 Changing User s Information 38 4 Ethernet Only Communications 4 1 Introduction 41 4 2 S...

Page 6: ...nal Measurements 65 7 2 Configuration Utility Setup 66 7 3 Selecting the Desired Measurements 66 7 4 Selecting Units for AI Blocks 68 7 5 Resetting Instrument Totalizers 69 7 6 Function Block Applicat...

Page 7: ...re followed carefully WARNING This symbol indicates a risk of potential serious personal injury unless these instructions are followed carefully WARNING It is the responsibility of the user to make su...

Page 8: ...Equipment WEEE take back initiative directive 2012 19 EU The equipment that you bought has required the extraction and use of natural resources for its production It may contain hazardous substances...

Page 9: ...Figure 17 tif 300 dpi 36 Graphics Figure 18 tif 300 dpi 37 Graphics Figure 19 tif 300 dpi 38 Graphics Figure 20 tif 39 Graphics Figure 21 tif 180 dpi 41 Graphics Figure 22 tif 300 dpi 41 Graphics Fig...

Page 10: ...s Figure 52 tif 150 dpi 70 Graphics NE107_Failed tif 150 dpi 71 Graphics NE107_Out of Spec tif 150 dpi 71 Graphics NE107_Maintenance Required tif 150 dpi 71 Graphics NE107_Check Function tif 150 dpi 7...

Page 11: ...d the flow transmitter can send flow data and diagnostic information to a flow computer or SCADA serially using a Gould type RTU protocol In this case only the MODBUS function command 3 read multiple...

Page 12: ...s to the corresponding terminals at the control system Note If two MODBUS option cards are installed in the flowmeter only the card in slot 5 is activated 1 3 Setting Up MODBUS Communications To set u...

Page 13: ...select it BAUD RATE current value appears here UART bits current setting appears here 8 no 8 odd 8even 7 no Table 1 UART Bits Options Option Bar Data Bits Stop Bits Parity 8 no 8 0 None 8 odd 8 0 Odd...

Page 14: ...2 Channel liquid flowmeter DF868 XMT868i Table 6 on page 14 for a Sentinel flowmeter Refer to Notes on page 8 page 13 or page 16 for information about the numerical references Note Depending on the t...

Page 15: ...Mass Totals Register 20 4 32 bit Long Integer 20 MT DIGITS Mass Tot Digits 0 2 21 22 Timer 2 4 32 bit Long Integer 23 9 Error Code 0 2 24 25 Sound Speed 3 4 32 bit Long Integer 26 27 10Density 4 4 32...

Page 16: ...ter MODBUS Reg Description Scaling decimal places Size in Bytes 1 1 Clear Ch1 Totalizers 2 16 bit signed int 2 1 Clear Ch2 Totalizers 2 16 bit signed int 3 4 Ch1 Velocity 2 4 32 bit Long Integer 5 6 2...

Page 17: ...c 4 IEEE 32 bit Float 73 74 Avg Std Volumetric 4 IEEE 32 bit Float 75 76 Avg Fwd Totals Register 79 4 32 bit Long Integer 77 78 Avg Rev Totals Register 79 4 32 bit Long Integer 79 Avg Tot Digits 0 2 8...

Page 18: ...or 21 10mA for a 4 20mA range 112 113 CH2 SNR Up 4 IEEE 32 bit Float 114 115 CH2 SNR Down 4 IEEE 32 bit Float 508 6MODBUS baud rate 0 2 509 7MODBUS parity 0 2 510 8 MODBUS stop bits 0 2 511 MODBUS met...

Page 19: ...6 57 Power 4 IEEE 32 bit Float 58 59 Energy Register 62 4 32 bit Long Integer 60 61 Energy Register 62 4 32 bit Long Integer 62 Energy Digits 0 2 16 bit signed int 63 64 TempS 2 4 32 bit Long Integer...

Page 20: ...Reg 4 reading is 44d7 Reg 5 reading is 4000 Volumetric is 44d74000 which corresponds to 1722 The complete Long integer value is constructed by combining readings from the first register with the secon...

Page 21: ...28 4 32 bit Long Integer 28 CH 2 T Digits 0 2 16 bit signed int 29 30 CH 2 Totalizer Time 2 4 32 bit Long Integer 31 2 CH 2 Error Value 0 2 16 bit signed int 32 33 CH 2 SSUP 1 4 32 bit Long Integer 34...

Page 22: ...Slot 6 Input B 4 IEEE 32 bit Float 508 6 MODBUS baud rate 0 2 16 bit signed int 509 7 MODBUS parity 0 2 16 bit signed int 510 8MODBUS stop bits 0 2 16 bit signed int 511 MODBUS meter addr 0 2 16 bit s...

Page 23: ...l 2 value if channel 1 is in error zero if both channels are in error 4 Average Error Status 0 both in error 1 chan 2 in error 2 chan 1 in error 3 both ok 5 MODBUS baud rate 5 2400 6 4800 7 9600 6 MOD...

Page 24: ...orward Energy Total 0 J 5s 4 IEEE 32 bit Float 36 37 Reverse Energy Total 0 J 5s 4 IEEE 32 bit Float 38 39 Pressure 105 Pa 10s Fixed 4 IEEE 32 bit Float 40 41 Temperature 20 C 10s Fixed 4 IEEE 32 bit...

Page 25: ...ow Limit 20 dB On Init 2 16 bit Int 77 Amplitude High Limit 95 On Init 2 16 bit Int 78 Amplitude Low Limit 35 On Init 2 16 bit Int 79 Number in Average 32 On Init 2 16 bit Int 80 Software Version 2 AS...

Page 26: ...or controller is of the form time delimiter Addr 3 Byte count Data CRC Low CRC High time delimiter Table 6 on page 14 is the data map for the IGM878 and Sentinel The refresh rate indicates how often...

Page 27: ...075 0x081A 3099 0x0C1A 4123 0x101A DN DAC U 2 Unsigned integer 29 0x001C 1053 0x041C 2077 0x081C 3101 0x0C1C 4125 0x101C UP Amp F 2 LSW float 31 0x001E 1055 0x041E 2079 0x081E 3103 0x0C1E 4127 0x101E...

Page 28: ...213 0X0C8C 4237 0X108C FWD Energy D 4 LSW 145 0x0090 1169 0X0490 2193 0X0890 3217 0X0C90 4241 0X1090 REV Energy D 4 LSW 149 0x0094 1173 0X0494 2197 0X0894 3221 0X0C94 4245 0X1094 Totl Time D 4 LSW 153...

Page 29: ...ettings Word Order I 1 Unsigned integer 5121 0x1400 Baud Rate I 1 Unsigned integer 5122 0x1401 Parity I 1 Unsigned integer 5123 0x1402 Stop Bits I 1 Unsigned integer 5124 0x1403 Meter Address I 1 Unsi...

Page 30: ...t number specified in IEEE Standard for Binary Floating Point Arithmetic ANSI IEEE Std 754 1985 also known as IEC60559 1989 Binary floating point arithmetic for microprocessor systems D Double precisi...

Page 31: ...option bar choices Fx represent function keys to select option bar choices Baud Rate RS232 19200 F2 9600 F3 600 F1 300 4800 F2 F3 1200 F4 2400 F1 COMM 2 Ch Meter GLOBL 1 Ch Meter 8 odd 8 no F1 F2 8eve...

Page 32: ...ading from two registers Some applications allow you to swap the registers Some do not When using the Modscan32 utility in order to monitor register values you need to select 03 HOLDING REGISTER see F...

Page 33: ...23 Chapter 1 Modbus Communications 1 5 Swapping the Floating Point cont To see all the register readings in Hexadecimal form select Menu Setup Display Options Hex see Figure 4 Figure 4 Finding the Hex...

Page 34: ...ptions User s Guide 1 5 Swapping Floating Point cont To monitor the floating point variable enter the first register of the variable in the Address see Figure 7 and set the Length to 2 Figure 5 The Ma...

Page 35: ...Swapping the Floating Point cont Then select Menu Setup Display Options Swapped FP see Figure 6 Modscan32 will swap the register and display the floating point variable correctly Figure 6 Swapped Floa...

Page 36: ...into floating point values see Figure 7 Note How to construct an 8 digit hexadecimal value from two registers is explained at the bottom of the Modbus Register tables Table 2 on page 5 for 1 Channel...

Page 37: ...s document provides instructions for setting up a flowmeter equipped with Modbus Over Ethernet Modbus TCP communications To apply these procedures the flowmeter must have the option card installed The...

Page 38: ...amples 2 2 1 Finding the Assigned IP Address Example Find the IP address of a module with Media Access Control MAC address 00409d25da0b 1 Open a DOS command prompt Go to the directory containing the e...

Page 39: ...address 3 112 161 79 see Figure 11 1 Open a DOS command prompt 2 Type telnet 3 112 161 79 10000 and hit Enter 3 Enter the current Login and Password The factory defaults are root and Netsilicon Note...

Page 40: ...er 3 Enter the current Login and Password Note The Login and Password are case sensitive 4 From the Main Menu select 1 IP Parameters 5 From the IP Parameters menu select 1 IP Address 6 Enter the new s...

Page 41: ...Communications Options User s Guide 31 Chapter 2 Modbus Over Ethernet Communications 1 2 2 3 Changing IP Parameters cont Figure 12 Changing IP Parameters 1...

Page 42: ...Chapter 2 Modbus Over Ethernet Communications 1 32 Communications Options User s Guide 2 2 3 Changing IP Parameters cont Figure 13 Changing IP Parameters 2...

Page 43: ...gher 3 1 Introduction This document provides instructions for setting up a flowmeter equipped with Modbus Over Ethernet Modbus TCP communications To apply these procedures the flowmeter must have the...

Page 44: ...select Microsoft Windows NT 4 0 2000 or XP Then under the window select Device Discovery Utility for Windows and the File Download window appears 5 Select Save this file to a disk click on OK and sav...

Page 45: ...le with Media Access Control MAC address 00409d24ded5 1 Run the Digi Device Discovery Program see Figure 16 Note To access the Digi Device Discovery Program see page 34 Note The MAC address of all fou...

Page 46: ...nding device and select Open web interface 3 Enter Username and Password Factory defaults are root and dbps Note The username and password are case sensitive PanemetricsPanemetrics recommends changing...

Page 47: ...Communications Options User s Guide 37 Chapter 3 Modbus Over Ethernet Communications 2 3 Accept incoming Modbus TCP in UDP IP UDP Port XXX 4 Apply Figure 18 Changing Modbus TCP Port...

Page 48: ...lect Open web interface 2 Enter the Username and Password The factory defaults are root and dbps Note The username and password are case sensitive Panemetrics recommends changing the default password...

Page 49: ...in the box delete the current password and type in the new password 8 To Confirm the new Password click in the box delete the current password and type in the new password Note For the password to be...

Page 50: ...Chapter 3 Modbus Over Ethernet Communications 2 40 Communications Options User s Guide no content intended for this page...

Page 51: ...tting up a flowmeter equipped with Ethernet Only communications To apply these procedures the flowmeter must have the option card installed See the option card examples in Figure 21 and Figure 22 Note...

Page 52: ...enu 3 Open the Select Your Product for Support menu and select Digi Connect ME Then click on Submit 4 From the OS Specific Diagnostics Utilities and MIBs menu select Microsoft Windows NT 4 0 2000 or X...

Page 53: ...Media Access Control MAC address 00409d24ded5 1 Run the Digi Device Discovery Program see Figure 23 Note To access the Digi Device Discovery Program refer to page 42 Note The MAC address of all found...

Page 54: ...nd password are case sensitive Panemetrics recommends changing the default password and disabling unused ports and services 3 Click on Login 4 Select Configuration Network 5 Select Use the following I...

Page 55: ...The username and password are case sensitive Panemetrics recommends changing the default password and disabling unused ports and services 3 Click on Login Figure 25 appears 4 Select Configuration Use...

Page 56: ...he box delete the current password and type in the new password 8 To Confirm the new Password click in the box delete the current password and type in the new password Note For the password to be chan...

Page 57: ...the flowmeter must have the option card installed see the example in Figure 27 and connected to a WI FI antenna Note To install an option card consult the user s manual s which apply to your instrume...

Page 58: ...Chapter 5 Modbus Over WI FI Communications 48 Communications Options User s Guide 5 2 WI FI Components cont Figure 29 WI FI Cable Antenna Connection Figure 30 WI FI Cable PC Board Connection...

Page 59: ...click on Submit 4 From the OS Specific Diagnostics Utilities and MIBs menu select Microsoft Windows NT 4 0 2000 or XP Then under the window select Device Discovery Utility for Windows and the File Do...

Page 60: ...with Media Access Control MAC address 00409d24ded5 1 Run the Digi Device Discovery Program see Figure 31 Note To access the Digi Device Discovery Program see page 49 Note The MAC address of all found...

Page 61: ...username and password are case sensitive Panemetrics recommends changing the default password and disabling unused ports and services 4 Click on Login 5 Select Configuration Network 6 Select Use the f...

Page 62: ...Chapter 5 Modbus Over WI FI Communications 52 Communications Options User s Guide 4 Apply Figure 33 Changing Modbus TCP Port...

Page 63: ...t Open web interface 2 Enter the Username and Password The factory defaults are root and dbps Note The username and password are case sensitive Panemetrics recommends changing the default password and...

Page 64: ...the box delete the current password and type in the new password 8 To Confirm the new Password click in the box delete the current password and type in the new password Note For the password to be ch...

Page 65: ...The higher the RSSI the stronger the performance a wireless system can provide Signal Strength is calculated by a wireless transceiver and can be viewed on Administration System Information WI FI LAN...

Page 66: ...Chapter 5 Modbus Over WI FI Communications 56 Communications Options User s Guide no content intended for this page Figure 37 System Information Menu WI FI Lan...

Page 67: ...flowmeter must have the option card installed see the example in Figure 38 and connected to a WI FI antenna Note To install an option card consult the user s manual s which apply to your instrument F...

Page 68: ...Chapter 6 WI FI Only Communications 58 Communications Options User s Guide 6 2 WI FI Components cont Figure 40 WI FI Cable Antenna Connection Figure 41 WI FI Cable PC Board Connection 6 3 Setup...

Page 69: ...pport menu and select Digi Connect ME Then click on Submit 4 From the OS Specific Diagnostics Utilities and MIBs menu select Microsoft Windows NT 4 0 2000 or XP Then under the window select Device Dis...

Page 70: ...h Media Access Control MAC address 00409d24ded5 1 Run the Digi Device Discovery Program see Figure 42 Note To access the Digi Device Discovery Program see page 59 Note The MAC address of all found uni...

Page 71: ...Note The username and password are case sensitive Panemetrics recommends changing the default password and disabling unused ports and services 4 Click on Login 5 Select Configuration Network 6 Select...

Page 72: ...he username and password are case sensitive Panemetrics recommends changing the default password and disabling unused ports and services 3 Click on Login Figure 44 appears 4 Select Configuration Users...

Page 73: ...e box delete the current password and type in the new password 8 To Confirm the new Password click in the box delete the current password and type in the new password Note For the password to be chang...

Page 74: ...The higher the RSSI the stronger the performance a wireless system can provide Signal Strength is calculated by a wireless transceiver and can be viewed on Administration System Information WI FI LAN...

Page 75: ...Avg Mass Flow MASS_U Ch1 Fwd Mass Totals MTOT_U Ch2 Fwd Mass Totals MTOT_U Avg Fwd Mass Totals MTOT_U Ch1 Rev Mass Totals MTOT_U Ch2 Rev Mass Totals MTOT_U Avg Rev Mass Totals MTOT_U Ch1 Mass Tot Dig...

Page 76: ...he OOS out of service mode before executing 7 3 Selecting the Desired Measurements To set the measurement unit for each AI 1 Double click on the FLOW Transducer Block in the tree under GEFlow XMT 2 Se...

Page 77: ...on Fieldbus Communications 7 3 Selecting the Desired Measurements cont 4 After the desired measurements have been selected choose the unit system UNIT_SELECTOR that has been programmed in the flowmete...

Page 78: ...ck for which you wish to set the units in the tree under GEFlow XMT see Figure 48 on page 66 2 Select the Scaling tab and set the unit for the measurement based on the flowmeter settings For example i...

Page 79: ...lick on the FLOW transducer block in the tree under GEFlow XMT see Figure 48 on page 66 2 Select the Others tab and scroll down to the CLEAR_TOTALIZERS listing 3 Select Clear from the drop down list b...

Page 80: ...up using the Function Block Application editor The flowmeter AI blocks along with the AO and PID of another device on the network are displayed We have connected the AI_1 OUT of the flowmeter to the C...

Page 81: ...1 Channel 2 and Channel Average Status Icons Cod e Error Range Default Value FD_FAIL_MAP FD_OFFSET_MAP FD_MAIN_MAP FD_CHECK_MAP E1 Low Signal 20 100 20 X E2 Sound Speed 1 to 50 20 X E3 Velocity Range...

Page 82: ...Chapter 7 Foundation Fieldbus Communications 72 Communications Options User s Guide no content intended for this page...

Page 83: ...option card in your flowmeter complete the following steps 1 Disconnect the main power from the flowmeter 2 Refer to your User s Manual for step by step instructions and install the HART option card...

Page 84: ...talled HART option card require no special setup procedures by the user The meter automatically configures itself for HART communication on startup However for field installation of a HART option card...

Page 85: ...l only those unit types listed in Table 11 are acceptable If a meter parameter is set to any other measurement units the HART device displays an Unknown Enumerator Can not resolve error message and ma...

Page 86: ...ls all inputs as channel specific For example a Slot 1 analog input that is programmed at the meter as a temperature input assigned to Channel 1 Channel 2 Both or Neither is always reported by the HAR...

Page 87: ...gy f p R if energy N N N Ch1 Ch2 or Ave energy f p R if energy N N N Ch1 or Ch2 Ssup f p R Y Y Y Y Ch1 or Ch2 ssDO f p R Y Y Y Y Ch1 Ch2 or Ave tUP f p R Y Y Y Y Ch1 Ch2 or Ave tDO f p R Y Y Y Y Ch1 C...

Page 88: ...N N Ch1 Max Sound Spd f p B Y N N N CH2 Information if applicable Ch2 Fixed Temp f p B N Y Y Y Ch2 Fixed Press f p B N Y Y Y Ch2 Tracking int B Y N N Ch2 Min Sound Spd f p B Y N N N Ch2 Max Sound Spd...

Page 89: ...char24 B Y Y Y Y Tag uchar6 B Y Y Y Y Descriptor uchar12 B Y Y Y Y Date uchar3 B Y Y Y Y Final Assy No uchar3 B Y Y Y Y Derial No uchar3 R Y Y Y Y Pvt Label Dist uchar R Y Y Y Y Pri Var Code uchar R Y...

Page 90: ...Chapter 8 HART Communications 80 Communications Options User s Guide no content intended for this page...

Page 91: ...pped with BACNet Over Ethernet communications To apply these procedures the flowmeter must have the option card installed The option card based on the features that were ordered will have many compone...

Page 92: ...et up the computer s IP parameters according to Figure 57 below Figure 57 Computer Cable Connection To set up the BACNet IP parameters enter 192 168 0 100 the default static IP of the board on your in...

Page 93: ...e ID see Figure 58 under Device Configuration click on Edit and a screen similar to Figure 59 appears Enter the flow meter type and or the device ID and click on Save Settings to save the change or Ca...

Page 94: ...IP address under Network Settings click on Edit and a screen similar to the following appears Enter the new address and click on Save Settings to save the change or Cancel Changes to return to the pr...

Page 95: ...d view data use any BACNet monitoring software The table shown in Figure 61 is used to monitor specific properties of certain objects on the CAS BACNet Explorer To add new objects to this list right c...

Page 96: ...Chapter 9 BACNet IP BACNet Over Ethernet 86 Communications Options User s Guide no content intended for this page...

Page 97: ...ular purpose and warranties arising from course of dealing or usage or trade Return Policy If a Panemetrics instrument malfunctions within the warranty period the following procedure must be completed...

Page 98: ...Warranty 88 Communications Options User s Guide no content intended for this page...

Page 99: ......

Page 100: ...uct and company names are trademarks of their respective holders 916 115 F Customer Support Centers U S A The Boston Center 1100 Technology Park Drive Billerica MA 01821 U S A Tel 800 833 9438 toll fr...

Reviews: