Masoneilan SVI II AP Digital Positioner Quick Start Guide | 64
Configuration
Use the procedures that follow to: calibrate, tune, view
configuration data and status messages for the SVI II AP.
Observe all warnings as the valve moves during these
procedures.
WARNING
These procedures can cause the valve to move.
Before proceeding be sure the valve is isolated from
the process. Keep hands clear from moving parts.
NOTE
All calibration and configuration procedures are
described using an SVI II AP with pushbuttons and
display and ValVue software.
NOTE
Starting with firmware version 3.2.7/5.1.3, if Autotune
is unsuccessful the message TuneERR appears on
the pushbutton display or when using the DD. Previ-
ous firmware versions reported this as TuneFail.
These messages do not mean the positioner is defec-
tive but indicate a need to perform a manual tune.