background image

Copyright 2000 Baker Hughes Company.

4 | PV 411A Instruction Manual–English

vacuum priming sequence above a second time, to 

verify that any air in the system has been removed.

7. The pump and connected system is ready for use.

4.4.2  Pre-filling

1. Connect the equipment as detailed “Operation” on 

page

 

2.

2. Turn the selector valve fully clockwise (in) position.
3. Loosen the reservoir cover lock nut (1) to open the 

reservoir cover (2) and let atmospheric pressure into 

the top of the reservoir.

4. Open the bleed valve on the UUT.
5. Carefully operate the scissor-action handles to fill the 

system. Stop pumping when fluid comes out of the 

bleed valve.

6. Close the bleed valve on the UUT.
7. If necessary, top-up the reservoir to the 2/3 level with 

clean fluid.

8. Secure the reservoir cover by tightening the reservoir 

cover lock nut (1).

9. The pump and connected system is ready for use.

4.5  Generating Hydraulic Pressure 

(Figure

 

A1)

Note: 

Pressurizing a fluid generates heat. A fluid heated or 

cooled in an enclosed volume causes a pressure change. 

Allow enough time to thermally stabilize.
1. If necessary, set the PRV see following section.
2. Open the selector valve (7) counterclockwise 1 turn.
3. Screw the volume adjuster (3) fully out 

(counterclockwise).

4. Close the selector valve (7).
5. Use the scissor-action handles (5) to generate the 

initial pressure.

6. Then turn the volume adjuster (3) clockwise to 

generate the required pressure, allow time for thermal 

stabilization.

7. To reduce the pressure, turn the volume adjuster (3) 

out (counterclockwise) to the required pressure.

8. After completion, turn the volume adjuster (3) fully out 

(counterclockwise) and turn the selector valve (7) to 

depressurize the pump. Disconnect from the pipes and 

equipment.

4.6  Setting Pressure Relief Valve 

(Figure

 

A3)

The pressure relief valve (PRV) can be set at pressures 

from 30 to 700 bar (500 to 10,000 psi).

If the system pressure exceeds the set pressure, the PRV 

opens and vents fluid through the inlet port to the reservoir. 

When the system pressure decreases below the set 

pressure, the PRV closes.

Key to Figure

 

A3

1. PRV locking screw (quantity 2)
2. PRV lock nut (with left-hand thread)
3. PRV adjusting nut (with left-hand thread)

4.6.1  To set the PRV:

1. Connect a suitable pressure indicator to either outlet 

port (Figure

 

A1) (2) or (6). Fit a blank to the unused 

port.

2. Increase pressure until the relief valve operates.
3. Loosen the two PRV locking screws (1).
4. Loosen the PRV lock nut (2) by turning clockwise.
5. Set the relief pressure by turning the PRV adjusting nut 

(3).
To increase pressure: Turn the PRV adjusting nut (3) 

counterclockwise.
To decrease pressure: Turn the PRV adjusting nut (3) 

clockwise.

6. After setting the PRV, hold adjusting nut (3) in position 

and tighten the locking nut (2).

Note: 

The locking nut has a left-hand thread.

7. Check the operation of the PRV. If necessary reset the 

PRV.

8. Secure the locking nut by tightening the two locking 

screws (1).

4.7  Fault Finding

If the system pressure reduces, check the following:
1. Check the selector valve (Figure

 

A1) (7) is in the

correct position and properly tightened.

2. Allow sufficient time after pressure generation for the 

temperature to stabilize. The larger the system volume, 

the longer the time for thermal stability.

3. Check the adaptors, flexible pipe and connections 

between the pump and equipment under test for leaks. 

Tighten any loose joints and replace any seals that are 

worn or damaged.

4. In hydraulic mode, if the volume adjuster can be wound 

fully in, but maximum pressure cannot be achieved, or, 

if pressure can be achieved, but an initial slow 

reduction appears to be present, there is probably air 

trapped in the system. Without disconnecting any 

pump or DUT connections, Re-prime using the vacuum 

priming method and repeat.

5. Check PRV pressure setting.
If, for any reason, a fault occurs within the pump, it is 

recommended that the equipment be returned to an 

appointed agent.

CAUTION  

Do not exceed 700 bar (10,000 

psi). This can damage the internal seals of the 

PRV and the PV

 

411A

Summary of Contents for Druck PV411

Page 1: ...PV 411A Pneumatic Hydraulic Hand pump Instruction Manual www tradinco com...

Page 2: ...Copyright 2000 Baker Hughes Company English PV 411A Instruction Manual i 8 3 1 7 6 2 3 5 4 A1...

Page 3: ...Copyright 2000 Baker Hughes Company ii PV 411A Instruction Manual English 1 2 4 3 2 3 1 A2 A3...

Page 4: ...Copyright 2000 Baker Hughes Company English PV 411A Instruction Manual iii A4...

Page 5: ...Copyright 2000 Baker Hughes Company iv PV 411A Instruction Manual English...

Page 6: ...or hydraulic pressure The scissor action handles provide pneumatic pressure and vacuum generation and in the hydraulic mode provides hydraulic pressure generation for system priming 1 1 Pneumatic Pum...

Page 7: ...y turn the selector valve to the center position 2 4 Scissor action Handles Limit Adjuster Figure A1 Turning the limit adjuster 4 clockwise reduces the stroke of the scissor action handles 5 turning t...

Page 8: ...pressure harmlessly in the event of inadvertent pressurization The reservoir connects to the inlet port on the top of the pump and supplies fluid to the pump system for pressure generation In vacuum m...

Page 9: ...pressure the PRV opens and vents fluid through the inlet port to the reservoir When the system pressure decreases below the set pressure the PRV closes Key to Figure A3 1 PRV locking screw quantity 2...

Page 10: ...g 6 2 Approved Service Agents For the list of service centers Druck com INFORMATION Hydraulic fluids must be compatible with stainless steel anodized aluminum nitrile rubber PTFE polypropylene Delrin...

Page 11: ...2000 Baker Hughes Company This material contains one or more registered trademarks of Baker Hughes Company and its subsidiaries in one or more countries All third party product and company names are...

Reviews: