Becker Digital Natural Gas Positioner Instruction Manual | 75
© 2022 Baker Hughes Company. All rights reserved.
Input Config
Valve Actions
Logging & Alarms
Utilities/Firmware
Logging & Alarms
Limit Alarms
Remote Indicator
Reset Solenoid Cnt
Limit Alarms
Adjust Upper Limit
Adjust Lower Limit
Press UP or DOWN button
to select LOGGING &
ALARMS then press ENTER
button
Press UP or DOWN button
to select LIMIT ALARMS
then press ENTER button
Press UP or DOWN
button to select
ADJUST UPPER then
press ENTER button
Press UP or DOWN
button to select
ADJUST LOWER then
press ENTER button
Upper Limit Alarm
98%
Lower Limit Alarm
2%
Press UP or DOWN
button to adjust
value then press
ENTER button
Press UP or DOWN
button adjust value
then press ENTER
button
▼
▼
▼
▼
▼
▼
Logging and Alarms Menu
Limit Alarms
In some applications the valve may need to stay inside a specific prescribed region of operation. For this
situation the DNGP can be configured to give alarms when these limits are reached. To set the upper and
lower limit alarms follow the procedure given in the figure below.