Becker Digital Natural Gas Positioner Instruction Manual | 23
© 2022 Baker Hughes Company. All rights reserved.
Figure 1 - DNGP-EXP Aluminum Enclosure and 5/3 Solenoid Valve
Figure 2 - DNGP-REM (Plastic Enclosure)
Table 7 - Wire Size, Wire Resistance and Voltage Drop Information
Note: Check with wire manufacturer for more accurate resistance data.
Dedicated wiring for each DNGP unit is recommended.
Voltage drops greater than four Volts are not recommended.
Actual resistance of wire may differ based on wire characteristics and manufacturer.
Cover
Conduit Entrances
6 shown
Wire Size
Resistance per 1000’
Length of Wire (one way) for 4 V Drop
18 AWG
8.45
240’
16 AWG
5.29
380’
14 AWG
3.26
610’
12 AWG
2.05
980’
10 AWG
1.29 Ohms
1550’