OPERATING PROCEDURES
INIIT03 INFI-NET TO INFI-NET TRANSFER MODULE LEDs AND CONTROLS
I-E96-607A
4 - 7
Figure 4-3. INIIT03
Faceplate
Table 4-5. INIIT03 Red/Green Status LED States
LED State
Meaning
Off
No power to the IIT module or the machine fault timer is
disabled (jumper installed) and the module is running.
Solid green
The IIT module is in the execute mode.
Solid red
Hardware failure or configuration error, check Bank B
CPU LEDs for an error code.
Table 4-6. Bank A CPU LED States
LED State
8
7
6
5
4
3
2
1
Meaning
x
x
x
x
x
x
x
x
Module start-up, LEDs 1 through 8
sequence irregularly.
1
1
0
0
0
0
0
0
Primary transfer module, normal operation.
1
0
0
0
0
0
0
0
Backup transfer module, normal operation.
BANK A
CPU LEDS
BANK B
CPU LEDS
RED/GREEN
STATUS LED
STOP/RESET
SWITCH
T00204A
INIIT03
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8