TERMINATION MODULE CONFIGURATION (NIDS01)
INTRODUCTION
C - 2
I-E96-207A
®
Table C-1. NIDS01 Application Summary
Interfaces To
Connecting Cable
Application
Signal Type
Control Station
NDCS03 or IISAC01
NKTD01
24 VDC provides com-
munication between a
control module and a
control station.
Digital Indicator Station
NDIS01
NKTD01
Termination Module
NICS01
6634408 ribbon cable
Table C-2. NIDS01 Terminal Assignments
Terminal
Number
Assignment
1
Common
2
+24 VDC
3
Manual/Auto 2 Select
4
Lower 2
5
Raise/Lower 2 Common
6
Raise 2
7
Manual/Auto 2 Power
8
Manual/Auto 2 Common
9
Manual/Auto 1 Select
10
Lower 1
11
Raise/Lower 1 Common
12
Raise 1
13
Manual/Auto 1 Power
14
Manual/Auto 1 Common