FUNCTION CODE DEFINITIONS
ENHANCED ANALOG INPUT DEFINITION FUNCTION CODE (FC 216)
I-E96-301B
C - 7
Table C-7. FC 216 Input Signal Types
S4
Value
Definition
0
Undefined. Do not use.
x01
Type S thermocouple
x02
Type R thermocouple
x03
Type E thermocouple
x04
Type J thermocouple
x05
Type K thermocouple
x06
Type T thermocouple
x07
Chinese Type E thermocouple
x08
Chinese Type S thermocouple
x09
Type L thermocouple
x10
Type U thermocouple
x11
Type N (14 AWG) thermocouple
x12
Type N (28 AWG) thermocouple
x20
U.S. Lab. Standard 100 Ohm Platinum RTD
(TCR = 0.003926)
x21
U.S. Ind. Standard 100 Ohm Platinum RTD
(TCR = 0.003911)
x22
European Standard 100 Ohm Platinum RTD
(TCR = 0.003850)
x23
120 Ohm Chemically pure Nickel RTD (TCR = 0.00672)
x24
10 Ohm Copper RTD (TCR = 0.00427)
x25
Chinese 53 Ohm Copper RTD
x40
+1 to +5 V. 4-20 mA.
x41
-10 to +10 V.
x42
0 to +10 V.
x43
0 to +5 V.
x60
-100 to +100 mV.
x61
0 to +100 mV.
x99
User-specified Voltage Range (min. -10 V., max. +10 V.)
NOTES:
1. Any S4 value not listed is undefined and should not be used.
2. x = 0
Normally used for thermocouple inputs. S3 of FC 215 will be used as the cold junction
reference.
3. x = 1
For any input used as a remote cold junction reference. This input may be used as the
cold junction reference for other thermocouple inputs. If x=1, the channel output value is digitally
filtered to emulate the temperature coefficient of the terminal block. If x=1 and the input type is a
thermocouple, S3 of FC 215 is ignored and this input automatically uses the onboard cold junction
reference for compensation.