Page A8/9
Operating Instructions
BA 7020
Technical specifications subject to change without notice
Copyright according to ISO 16016
A4.8 CAO menu
C
onfiguration
Analog Outputs:
Configuration analog inputs.
Not relevant in standard mode because the configuration of analog outputs is predefined.
A4.9 CD menu
C
onfiguration
Digital:
Configuration of digital inputs and outputs
Not relevant in standard mode because the configuration of digital inputs and outputs is predefined.
A4.10 CA menu
C
onfiguration
Alarms:
Configuration of alarms
Only menu items relevant to standard operation are outlined here.
Abbreviation Written out
Parameter/Function
Explanation
AL1
Alarm 1
Limiting Value Alarm 1
The configured limiting value AL1 is
compared with AI1 (first 2EZ) in standard
mode. An alarm is issued when this limiting
value is underrun. AL1 is set either with DIP
switch 5 (see Chapter 6.3) or by entering 1
for FP1 (see Chapter A4.6). Breakaway end
positions, for example, can be reported with
limiting values smaller than 0% or larger than
100%. The alarm is suppressed with a value
of -22.0% or 122.0%
Default: 2.0%
Input range: -22.0% to 122.0%.
AL2
Alarm 2
Limiting Value Alarm 2
The configured limiting value AL2 is
compared with AI2 (second 2EZ) in standard
mode. An alarm is issued when this limiting
value is exceeded. AL2 is set either with DIP
switch 6 (see Chapter 6.3) or by entering 1
for FP2 (see Chapter A4.6). Breakaway end
positions, for example, can be reported with
limiting values smaller than 0% or larger than
100%. The alarm is suppressed with a value
of -22.0% or 122.0%
Default: 98.0%
Input range: -22.0% to 122.0%.