Programming
Page 35/51
MID_M2000_BA_02_1807
5.2.7 Info/Help
Error Counts
The following list gives you an overview about the kind and frequency of
various messages and hence provides a diagnostic of the counter or the
measuring point.
Prior to any diagnostic, we suggest to reset the individual parameters in
order to exclude impacts occurring due to installation, maintenance or
other anormal operation conditions.
You can reset the individual parameters by selecting them with the cursor
and by pressing
E
. Select “number“ and press
E
[J]. Select „store“ and
press again
E
.
Detector
The number of times an invalid detector condition has
been observed
Empty Pipe
The number of times an empty pipe condition has
been observed by the meter
Full Scale
The number of times the flow has exceeded the full
scale setting
Totalizer
The number of times the totalizers have exceeded
limits of the meter
Pulse Sync.
The number of times the pulse outputs have fallen out
of synchronization
ADC Interrupt
The number of times an analog input measurement
has been missed
ADC Range
The number of times the analog input measurement
range has been exceeded
System Error
A diagnostic system message indicating the reason
for a system reset
System Resets
The number of times the meter has been reset
System Reset
ID
Diagnostic information about a system reset as a
result of expired internal timers