INTRODUCTION

The Series 3100 Monitor is an economical, dual channel, full featured, digital rate and totalizing monitor, compete 

with set-point control, scaled pulse output, analog outputs, analog PID controller, USB, and RS485 Modbus and 

BACnet communication .
Panel mount is NEMA4X-rated, and conforms to DIN standard dimensions (96 mm x 96 mm) for meter size and panel cutout . 

An optional NEMA 4 wall mount will be available in the future . 
The back-lit, two-line by 16-character alphanumeric display can be configured by the user with factory preset or with  

user-defined units of measure . Any combination of two rates or totals from either input channel can be displayed at any one 

time, with the special feature of channel addition or subtraction . LEDs report relay status and digital communication .
Inputs are from any combination of two pulse, sine wave or linear analog input devices . 
Configuration is menu driven using the LCD/keypad interface, or USB computer connection, with multiple password gates to 

prevent unauthorized access, while allowing access to select features such as total and relay reset functions . 
Outputs include four Form C mechanical relays, one solid-state switch, two Analog Outputs, one USB, and one RS-485 with 

BACnet and Modbus protocols .

Advanced Standard Features

•  Easy to switch power supplies from 12…24V AC/DC to the optional 120/240V AC .
•  Nonvolatile memory; no battery backup is required .
•  Two independent pulse and analog input channels can be used separately or combined in addition or subtraction modes, 

for all display output functions .

•  Field-definable custom units of measure labeling and conversion factors .
•  Two line by 16-character 3/8” (7 .95mm) high back-lit display .
•  Front panel LEDs indicate status of each relay, pulse output, and Rx/Tx activity .
•  Simple front panel configuration with the option to use the USB port .
•  USB communication is a very powerful diagnostic and OEM tool .
•  Two level password protection; one to restrict setup access and one to protect totals .
•  Field-definable custom units of measure labeling and conversion factors .
•  A total of seven independent relay, pulse and analog outputs .
•  Powerful set-point control, with independent set and release point values, set and release delays, and latching functions 
•  Scaled pulse output with pulse width control .
•  Dual channel analog outputs are either current sinking or sourcing 4…20 mA or 0…20 mA . Current sourcing 0…20 mA 

permits external conversion to 0…5V DC or 0…10V DC .

•  PID process control using analog outputs .
•  RS-485 with Modbus and BACnet/MSTP protocols .
•  IIFR (Infinite impulse response filter) . Proprietary input signal smoothing .

3100 Series Ordering Matrix

Example: 3100

 - 

x

x

Series

Flow Monitor

3100

 - 

Power  
Supply

Low Voltage

0

12…24V AC/VDC
High Voltage

1

120/240V AC

Mounting

Panel Mount

0

Figure 1:  Ordering matrix

Introduction 

Page 5 

August 2014

CTL-UM-001026-EN-04

Summary of Contents for Impeller Data Industrial 3100 Series

Page 1: ...User Manual Data Industrial Series 3100 Dual Channel Monitor Controller Transmitter CTL UM 01026 EN 04 August 2014...

Page 2: ...Data Industrial Series 3100 Dual Channel Monitor Controller Transmitter Page ii August 2014...

Page 3: ...rm C Relay COM N O and N C 9 Normally Open Solid Switch 11 Analog Outputs 11 RS 485 Communication Wiring 12 USB Communications Port 12 Programming 13 Programming Flow Charts Relays 13 Key Pad Display...

Page 4: ...Troubleshooting 26 Trouble Codes 26 Specifications 27 Data Industrial Series 3100 Dual Channel Monitor Controller Transmitter Page iv August 2014...

Page 5: ...AC DC to the optional 120 240V AC Nonvolatile memory no battery backup is required Two independent pulse and analog input channels can be used separately or combined in addition or subtraction modes f...

Page 6: ...el Mount is designed for through panel mounting which allows access to the back of the unit The 3100 is secured to the panel by two draw brackets shown in Figure 2 below Wall Mount Badger Meter does n...

Page 7: ...he power supply to the Series 3100 terminal marked LV AC DC and connect the negative end of the power supply to the Series 3100 terminal marked LV AC DC Earth ground can be connected to the terminal m...

Page 8: ...ar panel terminals are used all parameters are set with the LCD keypad interface No internal or external jumpers switches or potentiometers require movement or adjustment Pulse Inputs Solid State Swit...

Page 9: ...our mechanical form C relays one solid state normally open N O switch closure two analog outputs RS 485 for Modbus and BACnet communications and a USB connector for configuration and other purposes Se...

Page 10: ...Figure 8 High flow shut down and normally open master valve Figure 9 High flow shut down with irrigation clock and normally closed master valve Installation Page 10 August 2014 CTL UM 001026 EN 04...

Page 11: ...o analog outputs Each is isolated and independent and can be configured for 0 20 mA or 4 20 mA This unique design permits external conversion to externally to 0 5V DC or 1 5V DC with a 250 ohm resisto...

Page 12: ...e 12 RS 485 communication wiring Modbus BACnet USB Communications Port Using the USB Port requires Windows HyperTerminal or other similar communications software Figure 13 USB port Installation Page 1...

Page 13: ...rogramming Flow Charts Relays The following block diagrams explain various programming areas and are organized as follows Figure 14 Model 3100 programming chart Programming Page 13 August 2014 CTL UM...

Page 14: ...Figure 15 Flow inputs Programming Page 14 August 2014 CTL UM 001026 EN 04...

Page 15: ...Figure 16 Relays pulse outputs Programming Page 15 August 2014 CTL UM 001026 EN 04...

Page 16: ...Figure 17 Analog inputs Programming Page 16 August 2014 CTL UM 001026 EN 04...

Page 17: ...Figure 18 RS 485 communication port Programming Page 17 August 2014 CTL UM 001026 EN 04...

Page 18: ...the MENU Button One each screen there are three Choices In this case RESET SETUP and DIAG selects RESET selects SETUP and selects DIAG RESET SETUP DIAG Main Set up screen accessed by press MENU One ea...

Page 19: ...u Enter Set point 1 00000000 Menu Enter Figure 19 Selection screen Option List Screens Units of measure is an example of an options list Press to scroll up the list and to scroll down through the list...

Page 20: ...her set point crossing before restarting the count from zero LATCH Locks relay in energized state If Latch is chosen once energized by the set point time delay the relay will remain energized until re...

Page 21: ...006 30007 4 Flow 2 Total Input Register 30008 30009 BACnet The Model 3100 can be configured to communicate on a BACnet RS 485 MSTP Master Slave Token Passing system Configuration is via the front pane...

Page 22: ...ata bits 1 stop bit no parity and no flow contr 6 When connected a symbol will appear in the upper left corner of the main HyperTerminal display screen 7 Press the Enter Key Both the Rx and Tx LED s o...

Page 23: ...ore amenable to scripting it still accepts the same commands Any command entered without an sign and variable will display the current setting Example Typing display line 1 returns 0 which is the vari...

Page 24: ...low rate min current flow 1 2 sensor avg 0 100 averaging time constant in seconds flow 1 2 rate units 0 19 flow channel rate units to display 0 GPM 1 gal s 2 gal hr 3 Mgal day 4 L s 5 LPM 6 L hr 7 ft3...

Page 25: ...1 5 rate x totalizer rate relay 1 5 ctime 0 10000 pulse width in milliseconds relay 1 4 latch on off turn on off relay latching relay 1 4 setpoint x relay 1 4 setpoint x relay 1 4 relpoint x relay 1...

Page 26: ...reading from analog input AD converter channel 1 32 Error reading from analog input AD converter channel 2 36 Error writing to analog input AD converter channel 1 37 Error writing to analog input AD...

Page 27: ...r sourcing Sinking 30V DS 0 mA max 3 V 20 mA min Sourcing 600 max load USB Communication Provides complete access to all programming and operation features Requirements USB 2 0 A to Mini B five pin ca...

Page 28: ...ico Badger Meter de las Americas S A de C V Pedro Luis Ogaz n N 32 Esq Angelina N 24 Colonia Guadalupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Middle East and Africa Badger Meter Europa G...

Reviews: