Figure 64: Meter group
Select the Meter Group from the Group bar at the top of the screen . When the Meter pages appear select the flow page to
enter information about the flow units to be used .
Flow Page
Figure 65: Flow units setup
Flow Units Volume
Select an engineering unit for flow rate measurements:
US Gallons
Cubic Feet
Oil Barrels (42 Gallons)
Meters
Liters
Cubic Meters
Liquid Barrels (31 .5 Gallons)
Pounds
Mega US Gallons
Acre Foot
Feet
Kilograms
Table 13: Flow units
Flow Units Rate
Select a time interval for flow rate measurements: Seconds, Minutes, Hours, Days
Transmission Mode
Select the type of ultrasonic signal for the flow meter to generate:
• Hybrid – The DXN flow meter monitors the fluid conditions and determines automatically when to switch between
Doppler and transit time modes . Both transit time and Doppler transducers must be installed and connected .
If in Hybrid mode:
• If Transit Time signal quality is greater than 40%, Transit Time is used
• If Transit Time signal quality is greater than 10%, but less than 40%, and is still greater than Doppler Signal quality, Transit Time
is used
• If Transit Time signal quality is less than 10% and Doppler is greater than 10%, Doppler is used
• If either signal quality is less than 10%, there is no flow measurement
• Transit Time – The DXN flow meter always operates in transit time mode . If in Transit Time mode:
• If signal quality is less than 10%, there is no flow measurement
• Doppler – The DXN flow meter always operates in Doppler mode . If in Doppler mode:
• If signal quality is less than 10%, there is no flow measurement