4. Run Hyper-Terminal ( From the Windows Start Menu) and create a new connection, with a
name and ICON.
5. Configure this Port with 38400 baud, 8 data bits, 1 stop bit, no parity, and no flow control.
6.
When connected a “
> “ symbol will appear in the upper left corner of the main
HyperTerminal display screen.
7.
Press the “Enter Key”. Both the Rx and Tx LED’s on the front of the Series 3000 should
flash once, and
the “Badger Meter DIC … Software Version…” text message should appear.
The Series 3000 is now communicating ready to take commands from the list below.
Figure 3: COM4 properties screen
4 . Press ENTER . Both the Rx and Tx LEDs on the front of the Series 3100 flash once and the “Badger Meter DIC…Software
Version…” text message appears .
5 . The Series 3100 flow monitor is now communicating and ready to take commands from the list below .
USB Command List
In the list below, brackets indicate an argument, specifying its type and value range .
For instance [0-18] stands for any number between 0 and 18 (inclusive) .
Example
“display line1 = 1” sets Line 1 of the display to display #1, which is the totalizer for flow channel 1 .
Diagnostics
id -- show model number & software version
echo [on/off] -- turn on/off interactive command line:
with echo off, this interface is more amenable to scripting;
it still accepts the same commands .
Any command entered without an “ = " sign and variable will display the current setting .
Example: Typing “display line 1” returns “0” which is the variable for flow rate
read flow [1-2] -- read the current flow on channel 1 or 2 in GPM
read flow [1-2] total -- read the current total flow on channel 1 or 2 in gallons
comm mstpaddr = [0-127] -- BACnet/MSTP address
comm maxmaster = [0-127] -- BACnet/MSTP max master address
comm devinst = [x] -- BACnet device instance ID
comm mbslaveaddr = [0-255] -- Modbus slave address
Display Configuration
display line 1 = [0-1] -- set line 1 of the display
display line 2 = [0-1] -- set line 2 of the display
0: flow 1 rate
1: flow 1 total
3: flow 2 total
4: flow 1+2 rate
5: flow 1+2 total
6: flow 1-2 rate
7: flow 1-2 total
8: flow 2-1 rate
9: flow 2-1 total
display urate = [0 .1-10] -- set the update rate of the display, in seconds