1100-2294 Rev 1
28
17. , of this manual.
18. Click
Network Config
, and then press
“Upload CSV”
to upload the floorplan
spreadsheet
data.csv
from the root folder of the USB stick.
A success message will indicate that the upload is complete.
4.4 Commissioning
Each MVR-300 ships with default Modbus ID set to 1. These can be set in either of two
methods:
1.
Modbus ID Auto-assign:
Automatically connect and set ID’s using the integrated Magnetic Switch to pair each
MVR-300 to its install location.
2.
Set Modbus ID Manually:
Use the RS485 port on the controller to manually set the Modbus IDs, and then install
according to the floorplan, while keeping track of assigned Modbus IDs.
4.5 Method 1: Modbus ID Auto-assign
1. MVR-300 devices can be auto-assigned their Modbus ID using 2-person verification
technique.
This process gives that added advantage of physically verifying that each connected
device is correctly installed in the assigned room location.
2. Enter settings to confirm passcode has been entered. (If the passcode has not been
entered, the
Device Modbus Pairing
Screen will not be accessible).