6209-9000 Rev 2
17
4.2. Wiring the IAM-100 Controller
Open the IAM-C by removing the two front cover screws. Remove the
metal faceplate and locate the connection terminals. To install the
IAM-C, refer to the network drawing (Figure 3) and wiring diagram
(Figure 8).
Step
Wiring Instructions for the IAM-C
1
Connect the Remote Panel output to an input of the upstream
IAM Controller (see Figure 8 and Figure 3) using two-wire
cable. The output is not polarity oriented. If an upstream IAM
Controller is not used, ignore this step.
2
Verify proper setting of the remote reset jumper (HD3) on
each networked IAM-C. Factory default is enabled. Note
that the remote reset jumper MUST be disabled on the
master panel.
3
Connect relay contacts to COM and either NO or NC as
required for one or both relays.
4
If used in your application, wire the optional alarm horn to
connector CN19 using the + and - guides in Figure 8 as a
reference.
5
Connect up to 16 IAM sensors (panel output CN6 in Figure 7)
to input connectors CN1 through CN16 on the IAM Controller
(Figure 8) using two-wire cable. The polarity does not matter.
Observe proper wire type and length limits as specified in
Figure 8.
6
Disable individual channels by installing a 2.2 K
Ω resister
across each unused terminal block. See input CN8 in
Figure 8.
7
Ensuring proper polarity, connect main power to terminal
CN17. The power cable should have a strain relief fitted. It is
recommended for the main power connection to be externally
switchable and fused. A 5A fuse rating is recommended.
Summary of Contents for IAM-100
Page 7: ...IAM 100 and Controller Manual 6209 9000 Rev 2 7 Figure 3 Sample Architecture Diagram ...
Page 14: ...IAM 100 and Controller Manual 14 6209 9000 Rev 2 Figure 6 Controller Housing ...
Page 34: ...IAM 100 and Controller Manual 34 6209 9000 Rev 2 ...
Page 35: ...IAM 100 and Controller Manual 6209 9000 Rev 2 35 ...