background image

Cautions

• 

CAUTION: 

BAC units are typically installed immediately after shipment and many operate year round. 

However, if the unit is to be stored for a prolonged period of time either before or after installation, 
certain precautions should be observed. For instance, covering the unit with a clear plastic 
tarpaulin during storage can trap heat inside the unit, potentially causing damage to the fill and 
other components. If units must be covered during storage, an opaque, reflective tarp should be 
used. For normal seasonal shutdowns, refer to the applicable section in this manual.

• 

CAUTION:

 All electrical, mechanical, and rotating machinery are potential hazards, particularly for 

those not familiar with their design, construction, and operation. Accordingly, use appropriate 
lockout procedures. Adequate safeguards (including the use of protective enclosures where 
necessary) should be taken with this equipment both to safeguard the public from injury and to 
prevent damage to the equipment, its associated system, and the premises.

• 

CAUTION:

 When reversing the direction of fan rotation, allow the fan to come to a complete stop 

before restarting the motor.

• 

CAUTION:

 Do not use oils containing detergents for bearing lubrication. Detergent oils will remove the 

graphite in the bearing sleeve and cause bearing failure. Also, do not disturb bearing alignment by 
tightening the bearing cap adjustment on a new unit, as it is torque adjusted at the factory.

• 

CAUTION:

 Do not use steam or high pressure water to clean PVC eliminators or materials other than steel.

• 

CAUTION:

 This equipment should never be operated without all fan screens, access panels, and access 

doors in place. For the protection of authorised service and maintenance personnel, install a lockable 
disconnect switch located within sight of the unit on each fan motor associated with the equipment.

• 

CAUTION:

 Pressure greater than 69 kPa may cause damage to the distribution system.

• 

CAUTION:

 Never use chloride or chlorine based solvents such as bleach or muriatic (hydrochloric) 

acid to clean stainless steel. It is important to rinse the surface with warm water and wipe with a 
dry cloth after cleaning.

Freeze Protection

These products must be protected against damage and/or reduced effectiveness due to possible freeze-up 
by mechanical and operational methods. Please refer to the product catalogue or contact the local BAC.

Summary of Contents for VX Series

Page 1: ...OPERATION MAINTENANCE MANUAL VX Series...

Page 2: ...VXT Cooling Towers VXI S Industrial Fluid Coolers VXC S Evaporative Condensers Heat Transfer Section Construction Details...

Page 3: ...VXT Cooling Towers VXI S Industrial Fluid Coolers and VXC S Evaporative Condensers VXI S VXC S Only VXT suction connection located where pump suction shown above Pan Section...

Page 4: ...horised service and maintenance personnel install each fan and pump motor associated with this equipment with a lockable disconnect switch located within sight of the cooling tower WARNING Do no servi...

Page 5: ...he fan to come to a complete stop before restarting the motor CAUTION Do not use oils containing detergents for bearing lubrication Detergent oils will remove the graphite in the bearing sleeve and ca...

Page 6: ...nd quarterly thereafter Type Service Start Up Monthly Every6 months Shutdown Annually Inspect general condition of the unit Clean Debris from Unit Clean and Flush Sump Clean Sump Strainer Check and ad...

Page 7: ...Seasonal Shutdown PART 2 Maintenance Procedures 7 Cold Water Sump 7 Make Up Valve 9 Fan Shaft Bearings 9 Ball Bearings 10 Spray Nozzles and Heat Transfer Section 11 Corrosion Protection 12 Locking Col...

Page 8: ...VX SERIES Operation and Maintenance INITIAL AND SEASONAL START UP AFTER 24 HOURS OPERATION SEASONAL SHUTDOWN 1...

Page 9: ...tely 10mm below the overflow level 10 On VXI S Industrial Fluid Coolers and VXC S Evaporative Condensers start the pump and check for the proper rotation as indicated by the arrow on the pump cover On...

Page 10: ...urs of operating under load the following services should be performed 1 Check the unit for any unusual noise or vibration 2 Check the operating water level in the cold water sump Adjust the make up f...

Page 11: ...d water sump with the sump strainers in place Leave the drain open so rain and melting snow will drain from the unit 3 Clean the sump strainers and re install 4 Lubricate the fan shaft and motor beari...

Page 12: ...ERIES Maintenance Procedures COLD WATER SUMP MAKE UP VALVE FAN SHAFT BEARINGS BALL BEARINGS SPRAY NOZZLES AND HEAT TRANSFER SECTION CORROSION PROTECTION LOCKING COLLARS ADJUSTABLE MOTOR BASE FAN DRIVE...

Page 13: ...The strainers can be removed by pulling the handle up and away from the outlet connection NOTE Do not use acid to clean the strainers Make Up Valve A float operated water make up See Figure 1 is furni...

Page 14: ...pressure and the quantity of water suspended in the tower during pump operation plus that contained in the water distribution system external piping and any heat exchangers which could drain to the t...

Page 15: ...5 also have intermediate ball bearing s located midway on the shaft Ball Bearings Under normal operating conditions the bearings should be greased every 2 000 operating hours or at least every six mon...

Page 16: ...lows 1 Shut off the fan but leave the pump running 2 Remove the eliminators 3 Check to see if the nozzles are producing the spray pattern shown in Figure 8 4 Clean any nozzles which are clogged If nec...

Page 17: ...or of the cooling tower is finished with an etch primer covered with a heavy duty fast drying enamel after fabrication These units should be inspected annually Inspect the inside of the tower for blem...

Page 18: ...9 1 Loosen the set screw 2 Using a drift pin or centrepunch tap the collar in the hole provided tangentially in the direction of rotation while holding the shaft 3 Retighten the set screw Figure 9 Loc...

Page 19: ...ent should be checked annually to ensure maximum belt life This can be done by placing a straightedge across both sheaves as shown in Figure 7 When the drive is properly aligned the straightedge will...

Page 20: ...VX SERIES Water Treatment BLEED OFF BIOLOGICAL CONTROL 3...

Page 21: ...heat transfer efficiency and increase system operating costs The degree to which dissolved solids and other impurities build up in the recirculating water may be defined as the cycles of concentration...

Page 22: ...this arrangement the rate of bleed can be adjusted using the valve in the bleed line and measured by filling a container of known volume while noting the time period The bleed rate and water quality...

Page 23: ...d administered on a regular basis thereafter in accordance with the supplier s instructions Liquid biocides may be added to the basin of the cooling tower in dilute form If a solid form of biocide is...

Page 24: ...VX SERIES Cold Weather Operation 4...

Page 25: ...ice formation in heat transfer sections during operation 3 Protection against coil freezing VXI S Industrial Fluid Coolers Cold weather applications should be reviewed with the B A C representative i...

Page 26: ...VX SERIES Factory Authorised Parts 5...

Page 27: ...gency situations shipment can usually be made within twenty four hours To order factory authorized parts contact your local Baltimore Aircoil representative Be sure to include the unit serial number w...

Page 28: ...TOWERS ICE THERMAL STORAGE EVAPORATIVE CONDENSERS HYBRID PRODUCTS PARTS SERVICES w w w B a l t i m o r e A i r c o i l c o m a u 120 Wisemans Ferry Road Somersby NSW 2250 Telephone Australia 1300 134...

Reviews: