background image

6

MAINTENANCE PROCEDURES

 1. Fan Sheave
 2. Belt
 3. Motor Sheave
 4. Deflection
 5. Straight Edge

New belts have to be re-tensioned after 24 hours operation.

If Belt tensioning is required, please proceed as follows:
1. Loosen the lock nuts on the Motor Base Adjusting Screws.
2. Turn the Motor Base Adjusting Screws clockwise to tension the

belt, or counter-clockwise to relieve belt tension. During
adjustment of belt tension the drives should be rotated several
times by hand to evenly distribute the tension throughout the
belt.

3. When the belt is properly tensioned, retighten the locking nuts

on the Motor Base Adjusting Screws.

Note: There should be no “chirp” or “squeal” when the fan motor is started.

DRIVE ALIGNMENT

Proper drive alignment ensures maximum belt life. Alignment is
checked for standard drives after correct belt tensioning by placing
a straightedge across both sheaves as shown in the Figure below.
When the drives are properly aligned the gap measured between
straightedge and sheave does not exceed 0,5 mm per 100 mm of
fan sheave diameter.

 1. Motor Sheave
 2. Fan Sheave
 3. Points of Contact

LOCKING COLLAR

The excentric locking collar of the bearing at the drive end ensures
that the inner bearing race is secured to the fan shaft. Locking
collars can be set using the following procedure. (See Figure below)
1. Stop fan(s) and remove side access panel(s).
2. Loosen the set screw.
3. Using a drift pin centerpunch, tap the collar (in the hole provided)

tangentially in the direction of rotation while holding the shaft.

4. Retighten the screw.
5. Install access panel(s) and start fan(s).

 1. Direction of Rotation
 2. Drift Pin: Tap the locking collar in direction of fan rotation until cam is 

locked.

 3. Tighten set screw.

ROTATION OF FAN(S) AND PUMP(S)

Fans must rotate without obstruction and both fans and pumps
must rotate in the correct direction, which is indicated by arrows on
the equipment. Check proper functioning as follows:
1. Stop fan(s) and pump(s).
2. Turn the fan by hand to ensure rotation without obstruction.

Remove obstruction, if present.

3. Start the pump(s) and check for the proper rotation as indicated

by the arrow on the pump cover. If rotation is wrong, stop pump
and correct electrical wiring.

4. Start the fan(s) and check for proper rotation as indicated by the

arrow on the fan housing. If rotation is wrong stop fan(s) and
correct fan motor wiring.

MOTOR VOLTAGE AND CURRENT

Check the voltage and the current of all three legs of the fan and
pump motors. The current should not exceed the nameplate rating.
After prolonged shutdown the motor insulation should be checked
with a megger insulation tester prior to restarting.

UNUSUAL NOISE AND VIBRATIONS

Unusual noise and/or vibration are the result of malfunctioning of
mechanical components or operational problems. If this occurs, a
thoroughful inspection of the entire unit followed by immediate
corrective action is needed. If required, consult your local BAC
Balticare representative for assistance.

GENERAL CONDITION OF THE EQUIPMENT

The inspection should focus on following areas:

- damage of corrosion protection 
- signs of scale formation or corrosion
- accumulation of dirt and debris
- presence of biofilms

Smaller damages of the corrosion protection can be repaired.
Gavanised steel components should be inspected for blemishes and
corrosion. Affected areas can be wire brushed and recoated with a
cold galvanising compound such as zinc rich compound.
If there is evidence of scale formation (more than 0,1 mm) or
corrosion, water treatment regime must be checked and adjusted
by the supplier.
Any dirt and debris need be removed following the CLEANING
PROCEDURES described in this manual (See page 9<).

Figure 3: Fan Belt Check and Adjustment

Figure 4: Checking sheave alignment

Inspections and Corrective Actions

Figure 5: Locking Collar Assembly

Summary of Contents for VTL

Page 1: ...guide to achieve these goals In addition to establishing the operating plan and the cooling system logbook it is recommended to conduct a cooling system risk analysis preferably by an independent thi...

Page 2: ...Water Distribution Section 3 High Efficiency Drift Eliminators 4 Fan 5 Fan shaft and bearing 6 Fan motor 7 Wet Deck Surface 8 Strainer 9 Water Make up Valve 10 Coil VTL Cooling Towers VFL Closed Circ...

Page 3: ...TOWERS VTL Maximum inlet pressure 0 5 bar Water inlet temperature max 55 C std fill or 65 C high temperature option For circulating water quality compatible with construction materials refer to secti...

Page 4: ...n in order to prevent white rust Passivation is the formation of a protective passive carbonate layer on galvanised steel surfaces On newly installed units to provide maximum protection from corrosion...

Page 5: ...oat Arm Assembly 5 Float Valve To make the initial setting adjust the wing nuts so that the valve is completely closed when the water level in the cold water sump is 13 mm below the overflow level Und...

Page 6: ...ps must rotate in the correct direction which is indicated by arrows on the equipment Check proper functioning as follows 1 Stop fan s and pump s 2 Turn the fan by hand to ensure rotation without obst...

Page 7: ...edure is as follows 1 Shut off the fan s but leave the pump s running 2 Check and adjust spray pressure if required not applicable for coil models with standard pumps 3 Remove the eliminators 4 Check...

Page 8: ...new grease appears at the seal In particular when extended lubrication lines are fitted ensure that ALL old grease is removed and that new grease is leaving the seal The bearings should be lubricated...

Page 9: ...r DISINFECTION Disinfection of your cooling system may be needed in case of high concentration of aerobic bacteria and or Legionella Disinfection is also recommended for evaporative cooling systems wi...

Page 10: ...the full factory warranty Factory authorized replacement parts are available normally within four days after receipt of an order In emergency cases shipment can be usually made within 24 hours To orde...

Page 11: ...uired to ensure a safe and efficient operation of your evaporative cooling products From a full range of risk assessment to selective water treatment training testing record keeping and annual system...

Page 12: ...Every Six Months Annually Shutdown Checks and Adjust ments Cold Water Basin and Strainers X X Operating level and make up X X Blow down X X Sump heater package X X Belt tension X X Drive alignment X X...

Page 13: ...NOTES 13...

Page 14: ...14 NOTES...

Page 15: ...NOTES 15...

Page 16: ...NCE AND MONITORING PROGRAMME www BaltimoreAircoil com info BaltimoreAircoil co za Baltimore Aircoil Comapy SA Pty Ltd Portland Road Phillipi Cape Town South Africa Baltimore Aircoil Company SA Pty Ltd...

Reviews: