GENERAL DESCRIPTION

Photoluminescent egress path marking systems are an 
important life safety requirement in current building 
codes. These systems allow for the safe and quick 
evacuation of buildings in the case of an emergency. 
They provide a routing system that is not dependent 
on electrical power that can easily be followed in dark 
and smoke-filled exit pathways.  

Introd Safety 

Please read the complete instructions carefully before beginning any work. To ensure proper 
installation and performance of the product, the following actions must be completed by the 
installing contractor. Failure to do so will affect product warranty. 

Transpor Storage 

o

 

Inspect all shipments and materials for missing or damaged components and hardware. 

o

 

Material must be stored in a clean, dry location. 

Preparation 

o

 

These signs are for interior use only and are suitable for a temperature range of +50 to 100 
degrees Fahrenheit.  

o

 

These signs are rated for a visibility of 100 feet when activated by a minimum five (5) foot-
candlelight source and can be used in both high-level and low-level applications.

  

 
 
 

GENERAL SAFETY PRECAUTIONS

 Improper selection, installation, or use can cause personal injury or property damage. It 

is solely the responsibility of the user, through its own analysis to select products suitable for their specific application 

requirements, ensure they are properly maintained, and limit their use to its intended purpose. Follow proper local, 

state and federal regulations for proper installation and operation requirements. 

Summary of Contents for Lume-A-Lite BEM-SLE100

Page 1: ... to do so will affect product warranty Transportation Storage o Inspect all shipments and materials for missing or damaged components and hardware o Material must be stored in a clean dry location Preparation o These signs are for interior use only and are suitable for a temperature range of 50 to 100 degrees Fahrenheit o These signs are rated for a visibility of 100 feet when activated by a minim...

Page 2: ... should then be confirmed as acceptable prior to the mounting bracket being fixed to the wall or ceiling o After installation is complete the visibility of the sign from all potential viewing angles and distances should be confirmed INSTALLATION One Sided Wall Mount Installation The photoluminescent exit sign shall be placed above doors through which occupants must pass to complete the exit path 1...

Page 3: ...ng Mount One or Two Sided Installation The photoluminescent exit sign shall be placed above doors through which occupants must pass to complete the exit path 1 Mark pilot hole locations on ceiling using mounting holes in mounting bracket 2 Drill pilot holes in ceiling surface 3 Level and mount bracket to ceiling using mounting hardware 4 Slide and snap exit face plate to back plate 5 Attach top of...

Page 4: ...ction properly o Reliable external illumination is always required during building occupancy MAINTENANCE o Maintain by cleaning as needed to prevent dirt etc from inhibiting the performance of the photoluminescent properties o The strip may be cleaned by using a damp cloth with mild non abrasive cleaners Do not use highly alkaline or acidic cleaners Rinse after applying cleaners and wipe with a cl...

Reviews: