18. Technical data PD4-M-DIM
15. Wiring diagrams
Typ
SM
FC
FM
PD4-M-DIM (Master)
92147
92247
92248
PD4-S (Slave)
92142
92254
92163
LUXOMAT
®
Remote control:
IR-PDim (incl. wall bracket)
92200
IR-PD-DIM-Mini 92098
Accessory:
BSK Ball basket guard 92199
Occupancy detectors – Covering IP23
92206
17. Article / Part nr. / Accessory
MAN 7
25
9
–
19
08
13
2–2
In case the sensing area of the
LUXOMAT
®
PD4-M-DIM
is too large or areas are being covered that should
not be monitored, the range can be reduced or limited
through use of the enclosed masking clips (e).
14. Exclude sources of interference
13. Range
10. Fully / Semi automatic mode
(for IR-PDim functions see page 1)
The system switches over when the “Light” push-button is
open (see remote control functions, page 1). Each time
a push-button is pressed, the current operating mode is
indicated:
Red lights for 3 sec.
= Fully automatic mode
Green lights for 3 sec. = Semi-automatic mode
Fully automatic operation
In this operating mode, the lighting switches automatically
on and off for increased comfort, depending on presence
and brightness.
Semiautomatic operation
In this operating condition, in order to gain increasedsav-
ings, the lighting is energized only after being manually
switched on. Switch-off takes place automatically.
The semiautomatic mode basically behaves like the fully
automatic. However, the difference is that switching-on must
always be carried out manually!
As many (closer-contact) buttons as desired can be wired in
parallel on the “S” button input (ON/OFF Dimm).
e
Walking across
Walking towards
Seated
24 m
8 m
6,40 m
24 m
360°
2,50 m
2
3
1
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
16. Connections
PD4-M-DIM-SM socket
PD4-M-DIM-FC/-FM
L
N
R
Slave
L'
L
S
N
– +
R
T1
N
L
+
–
E1
1-10 V
EB
Sensor and power supply in one case
Power supply:
230 V~
±
10 %
Power consumption:
< 1W
Ambient temperature:
-25°C to +50°C
Degree of protection/class:
SM IP54, FC and FM IP20 / II
Settings:
locally and by remote control
Light values - IR-PDim:
50 - 1500 Lux
Extension of the detection area:
with Slaves
Area of coverage:
circular 360°
Range of coverage Ø H 2.50 m / T = 18°C:
seated 6.40m / tangential 24 m /
radial 8 m
Recommended height for mounting:
2 - 3 m
Light measurement:
Mixed light, da artificial light
Lux values - Potentiometer:
10 - 2000 Lux
• Channel 1 for light-connection
Type of contact:
NOC/with pretravel tungsten contact
Contact load:
2300 W cos
ϕ
=1 /
1150 VA cos
ϕ
= 0.5, µ-Contact
Time-settings:
1 - 30 min. / Test
DIM-Output:
1 x (1-10 V)
Max. no. of series-connected electronic ballasts:
max. 50 electronic ballasts by one single supply with
max. 100 m cable run and a conductur cross-section of
0.75 mm²
Dimensions H x Ø [mm]
SM FC FM
PD4-M-DIM
76 x 101 103 x 97 84 x 97
Visible portion when built into ceiling:
30 x 97 mm
Version: v.01
Technical data PD4-Slave
Power supply:
230 V~
±
10 %
Impulse output:
Optocoupler max. 2 W
Impulse duration:
2 sec. or 9 sec.
Dimensions:
see above
Declaration of Conformity:
The product complies with the low
voltage recommendation 2006/95/EC and the EMV recommen-
dation 2004/108/EC.
12. Manual Switching
You can switch the lighting on and off manually by
pressing the pushbutton for a short time. It will stay on or
off as long as people are detected plus the configured
follow up time.
L
N
R
Slave
L'
L
S
N
N
– +
R
T1
N
L
+
–
E1
1-10 V
EB
11. Manual Dimming – Preset /User
(for IR-PDim functions see page 1)
Manual dimming –
Start the dim process by pressing the
push button „min/max“. Stop by pressing the push button
„eye“.
PRESET –
the luminance set point is set during start-up
operation by the installer and remains unchanged. The
luminance set- point configured through manual dimming is
only applied for the time being.
Caution:
The constant light regulation is now deactivated!
The currently set artificial light is retained independent of
the ambient/daylight brightness!
After switching off and then back on, the originally set
luminance set-point is reset = constant light regulation is
activated.
USER
The luminance set-point is changed upon each manual dim-
ming and re-adjusted by the user (Conformation through
relay clicking!) The constant light regulation remains
activated!
The system switches over when the “Doublelock” push-button
is open (see remote control functions, page 1). Each time
a push-button is pressed, the current operating mode is
indicated:
Red lights for 3 sec.
= Preset
Green lights for 3 sec. = User
max
50
Lux
1500
Lux
ON
OFF
Standard mode with master DIM occupancy detectors
L
N
E1 110 V EB
N
L
+
R
S
L L΄΄΄΄
N
+
N L
R
T1
C1
optional
T1 = NO button for semi-automatic mode
Slave for enlargement of detection area
WE RECOMMEND THAT BEFORE DIMMINg OF THE CONNECTED
LIgHTS A 100 h BURN IN (T5 TUBES OR 80 HOURS FOR T8 TUBES)
FUNCTION TAkES PLACE.
THE LIFESPAN OF THE LAMPS CAN BE REDUCED IF THE BURN IN
DOES NOT TAkE PLACE.
19. LED-functional indicators, fault-finding
The functional indicators in the case of the
LUXOMAT
®
PD4-M-DIM (red and green LED‘s)
Red LED indicating self-checking mode
(over a period of 60 seconds following mains‘-supply lock-on)
Flashing at intervals of 1 second
EEPROM
/memory empty
Flashing rapidly
EEPROM
/memory contains information
Red LED as an indicator of status
Flashing irregularly
Movements are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off (dependent upon operating mode)
Not illuminated
Detector identifies dark, light on (dependent upon operating mode)
Flashing extremely rapidly
Too bright / Too dark / Undefined
Red LED as an acknowledgement of receipt for commands from the
remote control
Illuminated for 2 seconds
Signal validly received
Illuminated for 0.5 seconds
Not-accepted command, detector blocked
Flashing extremely rapidly
Not-accepted command, occurs, for example, when an attempt
is made to input twilight-value are too bright or too dark
green LED as an acknowledgement of receipt for commands from
the remote control
Lights up for 3 seconds
Semi automatic or user signal correctly received
green LED as an indicator of status
(only for status “Permanent protection against sabotage”)
Flashing irregularly
Movement are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off (dependent upon operating mode)
Not illuminated
Detector identifies dark, light on (dependent upon operating mode)
lluminated for 2 seconds
Signal validly received (dependent upon operating mode)
White LED
Lights permanently
Semi-automatic active (shines)
Illuminates 4 seconds, then 1 sec off
Semi-automatic and active corridor
Illuminates 1 seconds, then 4 sec off
Only active corridor