Sensor and power supply in one case

Power supply:

 230 V~ +6 %/-10 %

Power consumption:

 < 1W

Ambient temperature:

 -25°C to +50°C

Degree of protection /class:

 SM IP54, FC and FM IP20 / II

Settings:  

locally and by remote control

Light values - IR-PD:

 10 - 2000 Lux

Extension of the detection area:

 with Slaves

Area of coverage:

 circular 360°

Range of coverage Ø H 2.50 m / T=18°C:

 

 

seated 2.50 m / tangential 10 m / radial 6 m

Recommended height for mounting:

 2 - 3 m

Light measurement:

 mixed light, da artificial light 

Lux values - Potentiometer:

 10 - 2000 Lux

• Relay/Channel 1 for light-connection

Type of contact

: NOC/with pretravel tungsten contact

Contact load:

 2300 W, 230 V~, 10 A cos (

ϕ)

=1 / 

1150 VA cos (

ϕ)

= 0.5 

DIM-Output:

 1 x (1-10 V)

Max. no. of series-connected electronic ballasts: 

max. 50 electronic ballasts by one single supply with  

max. 100 m cable run and a conductur cross-section of  

0.75 mm²

Time-settings:

 15 sec. - 16 min. (30 min. with remote

control) / test

Dimensions HxØ [mm]

 

SM 

FC 

FM

PD2-M-1C 

50 x 98  84,5 x 80  65 x 98

Visible portion when built into ceiling:

 34 x 79 mm

Technical data PD2-Slave

Electrical data same as above, but just one channel for 

signaling motion detection.

 

Declaration of Conformity: 

The product complies with 

the low voltage recommendation 2006/95/EC and the 

EMV recommendation 2004/108/EC

12. Technical data PD2-Master-1C

10. Wiring diagrams

Type

SM

FC

FM

PD2-M-1C

92550

92565

92555

LUXOMAT

®

 Remote control:

IR-PD (incl. wall bracket) 

92160

IR-PD-Mini 

 

92159

Accessory:

BSK Ball basket guard   

92199

Wall bracket for remote control as replacement  92100

Socket IP54 

 

92161

9. Article / Part nr. / Accessory

M

A

N 5

62

– 1

41

20

9-

4

In case the sensing area of the 

LUXOMAT

®

 PD2-M-

1C-SM is too large or areas are being covered that 

should not be monitored, the range can be reduced 

or limited through use of the enclosed masking 

clips (e).

8. Exclude sources of interference (PD2-M-1C-SM)

5.  Fully / Semi automatic mode 

(for IR-PD functions see page 1)

Fully automatic operation

In this operating mode, the lighting switches automati-

cally on and off for increased comfort, depending on 

presence and brightness.

Semiautomatic operation

(Semiautomatic can only be activated via the remote 

control!)

In this operating condition, in order to gain increased 

savings, the lighting is energized only after being manu-

ally switched on.

Switch-off takes place automatically.

The semiautomatic mode basically behaves like the fully 

automatic one. However, the difference is that switching-

on must always be carried out manually!

As many (closer-contact) buttons as desired can be wired 

in parallel on the “S” button input (ON/OFF).

13. LED-functional indicators, fault-finding

The functional indicators in the case of the 

LUXOMAT

®

 

PD2-M-1C-MASTER (red and green LED‘s)

Red LED indicating self-checking mode (over a period 

of 60 seconds following mains‘-supply lock-on)

Flashing at intervals of 1 second

 

EEPROM/memory empty

Flashing rapidly

EEPROM/memory contains information

Red LED as an indicator of status

Flashing irregularly

Movements are detected within the area of coverage

Flashing regularly

 Detector identifies bright, light off  

(dependent upon operating mode)

Not illuminated

 Detector identifies dark, light on  

(dependent upon operating mode)

Flashing extremely rapidly

Too bright / Too dark / Undefined

Red LED as an acknowledgement of receipt for  

commands from the remote control 

Illuminated for 2 seconds

Signal validly received

Illuminated for 0.5 seconds

 Not-accepted command, detector blocked

Flashing extremely rapidly

 

 Not-accepted command, occurs, for example, when 

an attempt is made to input twilight-value are too 

bright or too dark

Lights up for 3 seconds

Fully automatic mode

Flashing for 3 seconds

Semi automatic mode

Green LED as an indicator of status (only for status 

“Permanent protection against sabotage”

)

Flashing irregularly

 Movement are detected within the area of coverage

Flashing regularly

 Detector identifies bright, light off  

(dependent upon operating mode)

Not illuminated

 Detector identifies dark, light on  

(dependent upon operating mode)

lluminated for 2 seconds 

Signal validly received  

(dependent upon operating mode)

7. Range of Coverage

6. Manual Switching 

 

You can switch the lighting on and off manually by 

pressing the pushbutton for a short time. It will stay on or 

off as long as people are detected plus the configured 

follow up time.

max

50

Lux

1500

Lux

ON

OFF

11. PD2-M-1C - Connections

Connection PD2-M-1C-SM

Connection PD2-M-1C-FC/-FM

NO

NO

N

R

L L

SLAVE

S

3A

NO

NO

N

R

L L

S

SLAVE

3A

N

quer zum Melder gehen 
frontal zum Melder gehen
Unterkriechschutz

walking across
walking towards
seated

Master

Standard operation

Terminal connection for standard operation

S

Master

Standard operation

Terminal connection for standard operation

S

NO

NO

FC 

L
N

N  N   L   L   R   R

Master

Slave

Master-/Slave-operation with one Master and 

several Slaves. 

The Master is the only unit to read in the Lux levels and to 

switch  the  connected  loads.  The  Slave  units  will  react  on 

motion only, independently of the Lux levels, by sending an 

impulse via the dry contact, to the Master.

Terminal connection for Master-/Slave-operation

S

Master

Standard  operation, 

manual  switching  possible  (NO-

contact to be pressed for approx. 1sec.) The potentio meters

not to be set on “Test“ or “Sun“ otherwise the preadjusted 

values will get lost during this manual operation.

 Standard operation with external push button

S

SM

SM

10 m

6 m

2.50 m

10 m

360°

2.50 m

1

2