3. Putting into operation / Settings
Follow-up time for light control
The time can be set infinitely variably at between
15 seconds and 16 minutes.
Symbol : impulse < 1sec.
Symbol
TEST
: Test mode
(Every movement switches on the light for a period of 1
second, switching it off for a period of 2 seconds after that
regardless of the level of brightness.)
Twilight-switch for light control (relay 1)
The switch-on value for the light can be set at between 10
and 2000 Lux. Using the rotary control, the luminance set
points can be set as desired.
Symbol :
Night-time operation
Symbol : Daytime/Night-time operation
Installation and Operating Instruction for
B.E.G.
- Occupancy detectors PD2-M-1C-SM/-FC/-FM
The detector can be installed
in conventional inlet-sockets
mounted on the ceiling.
The assembly plate enclosed
must be stripped off prior to
installation and secured to the
ceiling using 4 screws and
ensuring that it is not laterally
transposed.
Having connected up the
cables in accordance with
regulations, the detector can
be placed in position as shown
in the drawing opposite and,
applying a little pressure, can
then be locked into position with the assistance of
the spring clips.
2a. Installation of the LUXOMAT
®
PD2-M-1C-SM
2c. Installation of the LUXOMAT
®
PD2-M-1C-FM
The detector must be in-
stalled on a solid and level
surface. There is no need
for frames.
For mounting remove lens
(C) (turn anticlockwise).
Fasten the mounting pod
to the ceiling.
Having connected up the wires in accordance
with regulations, secure the detector with 2
screws as per the illustration above. In order
to assemble the detector outside, the PD2-IP54
base-plate, which is available as an accessory,
must be mounted between the detector and the
surface on which it is to be installed.
Unlocking device
Lock device
4. Settings carried out using remote control (optional)
Remote control LUXOMAT IR-PD
1. Check Battery:
open battery compartment by pressing the
plastic springs together and removing the
battery-holder.
2. IMPORTANT
Please pay attention, that the setting is Potentio-
meter 1 at “TEST” and Potentiometer 2
not
at
“SUN”. All values which have been programmed
using the remote control will be deleted in the
event of power failure in the position “TEST/
SUN”. Please switch Potentiometer 2 over to
“MOON” or any other value.
Caution:
Settings with remote control supersede the
settings by courtesy of potentiometers.
LUXOMAT
®
PD2-M-1C
1. Mounting preparations
Work on the 230 V mains supply
may only be carried out by qualified
professionals or by instructed persons
under the direction and supervision
of qualified skilled electrical person-
nel in accordance with electrotechni-
cal regulations.
Disconnect supply before installing!
When in Master/Slave mode of
operation, the Master-appliance
must always be installed at the
location where there is least
daylight.
Lock device
Test mode
Reset to deactivate
Resetting when closed
The lighting relay is switched off, i.e.
opened and the follow-up times reset.
Permanent protection against sabotage
This function blocks the unit permanently (green LED is illuminated).
This operating mode can only be activated during the period of 5
seconds after pressing the “lock“ button. This status will only
permit actuating the function “Light on/Light off”.
The procedure for leaving this mode is as follows:
1. Switch off the current
2. Apply current for 31 – 59 seconds
3. Switch of the current again
4. Apply current
5. Open detector
Light on/off
The light will remain switched on/off for as long as movements
are detected in the areas of coverage. Once the last movement
has been detected, the light will remain on for the duration of the
follow-up time as per setting.
The appliance will then return independently to the mode selected
(Fully or Semi-automatic).
2b. Installation of the LUXOMAT
®
PD2-M-1C-FC
The detector has
been designed
and developed
specifically for instal-
lation in suspended
ceilings.
A circular opening of
diameter 68 – 70 mm
must be produced in
the ceiling.
Having connected up the cables in accor-
dance with regulations, the detector is
inserted into the opening as shown in the
drawing opposite and fixed into position with
the assistance of the spring clips.
Option:
Wall bracket for remote
control IR-PD
2d. Self test cycle
The product enters an initial 60-sec-
ond self-test cycle, when the supply
is first connected. The occupancy
detector is ready for operation.
��
���
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
����
���
��
��� ��
���
max
50
Lux
1500
Lux
ON
OFF
Luminance set point
Automatic reading in the current light value
as new luminance set point
Individual light value 2 - 2500 Lux
Follow-up time (relay and channel 1)
15 sec. up to 30 min.
Impulse function (relay and channel 1)
1sec. ON, 9 sec. OFF
Preset/user mode
Fully automatic/semi automatic mode => (see page 2, point 5)
Semi automatic: red LED (flashing),
Fully automatic: red LED on for approx. 3 sec.
Resetting when open
All values which have been programmed using the remote
control IR-PD are deleted, and those values which have
been set by potentiometer are activated.
120 6050
40
30
15
10
A
16 10
5
2
1
30
15
TEST
2000
1200
600
200
40
5
120 6050
40
30
15
10
A
16 10
5
2
1
30
15
TEST
2000
1200
600
200
40
5
GB