1. Product information
• Wall motion detector with acoustic sensor
• Indoor 180-R:
Relay version in 3-conductor engineering for
inductive, capacitive and ohmic loads
• Indoor 180-T:
Triac version with 2-wire technology, no neutral
• Indoor 180-T:
Only for resistive loads. Not suitable for LED
loads
• Individually adjustable acoustic sensor
• Automatic restart of follow-up time on movement and sound
• Available with surround (interior cover dimensions 60 x
60 mm) or without surround for use with faceplate (interior
cover dimensions 50 x 50 mm) in 5 different colours
• Centre plates are available for installation in different
manufacturers’ switch systems: see accessories
• Push button manual switching available
2. Operation
The motion detector switches the light automatically, depending
on people being present (movement) and on ambient light.
The motion detector switches the light on if the ambient light level
is below a brightness threshold (which can be set on the device)
and movement is detected.
The motion detector switches off again once no more movement
is detected within a follow-up time, i.e. it remains switched on as
long as it detects movements (independent of the light level).
As well as a PIR sensor for motion detection, the device also
has an additional acoustic sensor. Motion detection is always
required first for switching on the lighting. When it is switched
on, a follow-up time starts, which restarts when either sound or
motion is detected. After the follow-up time has expired and
therefore the lighting has switched off, there is an additional
duration of 9 sec. in which the lighting may be switched on
again by sound.
3. Safety information
!
Work on the 110 - 240 V mains supply may only be
carried out by qualified professionals or by instructed
persons under the direction and supervision of
qualified skilled electrical personnel in accordance
with electrotechnical regulations.
!
Disconnect supply before installing!
!
This device is not suitable for disconnection.
4. Mounting
(A)
Sensor insert
(B)
Mounting screws
(C)
Blinds for the exclusion of interference sources
(Animals, small children ...)
(D)
Frame
(E)
Cover
(F)
Cover-cap
(G)
Vandal-proofing of potentiometer cover against unwanted
removal
!
The connected load must not exceed the following values:
180-T (Triac version):
Incandescant / halogen lamps min. 40 - max. 300 W
180-R (Relay version):
2300 W, cos
ϕ
= 1
1150 VA, cos
ϕ
= 0,5
Install the unit in a protected position,
for wall mounting at a height of 1.10
to 2.20 m.
1m
Minimum distance to lighting being
controlled, to the front or to the side of
the unit: 1 m
X
X
X
X
Inappropriate installation or use will
interfere with trouble-free operation or
lead to damage to the unit.
X
Suitable for installation in a 60 mm
flush-mount box. The cable inlet should
be vertical.
5. Hardware configuration
Position LEDs and Potentiometer
(A)
(B)
(C)
I
II
Potentiometer
(A)
: Potentiometer for Brightness setting
Potentiometer
(B)
: Potentiometer for Acoustic sensor
Potentiometer
(C)
: Potentiometer for Follow-up time
LED
I
: red
LED
II
: red (Acoustic sensor)
6. Self test cycle/Startup behavior
The product enters an initial 60-second self-test cycle, when the
supply is first connected (LEDs flash).
7. Putting into operation/Settings
120 6050
40
30
15
10
A
16 10 5
2
1
30
15
TEST
2000
1200
600
200
40
5
Brightness threshold (Potentiometer A)
The brightness set value can be defined between
40 and 2000 Lux. Using the rotary control, the
luminance set points can be set as desired.
Symbol
: Night-time operation (10 Lux)
Symbol
: Day-time operation
(light evaluation inactive)
120 6050
40
30
15
10
A
16 10 5
2
1
30
15
TEST
2000
1200
600
200
40
5
Follow-up time for light control (Potentiometer B)
The time can be set infinitely variably between
15 sec. and 16 min.
Symbol
TEST
: test mode, only motion-dependent.
Every movement switches the light on for 1 sec.,
then off again for 2 sec.
Symbol : approx. 1 sec. on, 9 sec. off
Acoustic sensor
The sensitivity of the acoustic sensor is infinitely
adjustable with the rotary control (Left position =
max. sensitivity, Right position = acoustic sensor
off).
8. Wiring diagrams
Standard mode with 1-channel motion detectors Indoor 180-R
and optional arc extinction kit
RC
L
N
L
L
N
C1
E1
S1
R
T1
Optional
S1 = switch for permanent light
T1 = NO button, manual switching additionally possible
RC = RC-suppression kit if required
Standard mode with 2-wire technology, triac
L
N
L΄΄΄΄
L
C1
E1
S1
Optional
S1 = switch for permanent light
Operating and mounting instruction
B.E.G.
motion detector Indoor 180-R and Indoor 180-T
LUXOMAT
®
Indoor 180-R/-T
EN