background image

BL4, BL4-C

93288, 93284

Operating Manual

5

2.4

Disclaimer

B.E.G. Brück Electronic GmbH is not liable in the following cases:

The device is not being used properly.

Reasonably foreseeable misuse is not taken into account.

Mounting and electrical connection are not properly performed.

Changes (e.g., constructional) are made to the device.

Summary of Contents for Luxomat BL4

Page 1: ...Subject to technical changes Motion detector BL4 BL4 C Operating Manual 93288 93284...

Page 2: ...1789 Lindlar GERMANY Phone 49 0 2266 90121 0 Fax 49 0 2266 90121 50 E mail info beg de Internet beg luxomat com All device data can also be found here BL4 https www beg luxomat com qr php prtno 93288...

Page 3: ...tions 7 3 3 LED indicators 8 4 Mounting 9 4 1 Choice of mounting location 9 4 1 1 Mounting location BL4 9 4 1 2 Mounting location BL4 C 9 4 1 3 Sources of interference 10 4 1 4 Range 10 4 2 Mounting o...

Page 4: ...22 7 2 Maintenance 22 7 3 Disposing 22 8 Diagnostics and troubleshooting 23 9 Service and support 24 9 1 Manufacturer s warranty 24 9 1 1 Product code 24 9 2 Contact details 24 10 Technical Data 25 10...

Page 5: ...ions with a narrow elongated detection range especially for corridors Symbol indicating possible dangers to persons Symbol indicating possible property damage Symbol for useful information and tips NO...

Page 6: ...by instructed persons under the direction and supervision of a certified electrician in accordance with the elec trical engineering regulations Due to their technical training knowledge and experienc...

Page 7: ...r ck Electronic GmbH is not liable in the following cases The device is not being used properly Reasonably foreseeable misuse is not taken into account Mounting and electrical connection are not prope...

Page 8: ...x 1 5 mm2 removable 2 Locking unlocking TX10 for spring clip 1 3 Lens for circular detection area BL4 4 Lens for narrow detection area especially for corridors BL4 C 5 Marking sticker for corridor al...

Page 9: ...e below which the illumination is to be switched on can be freely selected switch on threshold If the value measured by the light sensor is below the set switch on threshold a detected move ment cause...

Page 10: ...test cycle Factory setting active Red green and white LEDs flash alternately Detector is programmed Red LED flashes quickly 2x s LED function indicators during operation Motion detection Red LED flas...

Page 11: ...BL4 C The BL4 C motion detector has a narrow detection range especially for corridors Mount the corridor ceiling motion detector so that the red marker arrow labels or Fresnel lens areas in the detect...

Page 12: ...With a switch on threshold greater than 1000 lux day mode sun setting the light evaluation is inactive i e the detector operates independently of brightness INFO Observe mounting height Please be sure...

Page 13: ...BL4 BL4 C 93288 93284 Operating Manual 11 4 2 Mounting options 4 2 1 Ceiling installation 4 2 2 Surface mounting with mounting set 93183 68 mm 1 2 1...

Page 14: ...Operating Manual BL4 BL4 C 93288 93284 12 2 3...

Page 15: ...BL4 BL4 C 93288 93284 Operating Manual 13 4 2 3 Flush mounting with mounting set 93194 4 1...

Page 16: ...Operating Manual BL4 BL4 C 93288 93284 14 2 3 4 5...

Page 17: ...ion and supervision of a certified electrician in accord ance with the electrical engineering regulations Disconnect supply before installing This device is not to be used to isolate other equipment f...

Page 18: ...ompartment Open the strain relief and carry out the electrical connection NOTICE Mount strain relief For ceiling mounting install the strain relief after the electrical connection has been made CAUTIO...

Page 19: ...rallel connection NOTICE Parallel connection Up to 8 detectors can be connected in parallel to extend the detection range For parallel connection connect all detectors to the same phase conductor 1 2...

Page 20: ...programmed or whether the factory settings are active NOTICE Interference suppression of the loads All switched loads must be properly suppressed We recommend our RC suppressor units see accessories...

Page 21: ...for programming The settings for the day night operation the switch on threshold the follow up time the detection sensitivity and the status LEDs can then be made The procedure is ter minated automat...

Page 22: ...ness value below which the illumination is switched on is called the switch on threshold The switch on threshold can be selected between 20 Lux and 1000 Lux Below this value the illumination is switch...

Page 23: ...e device Activate the programming mode Select switch on threshold or read in current light value as new switch on threshold Follow up time illumination 15 s 60 min Detection sensitivity Low LOW Medium...

Page 24: ...ce must only be carried out by the manufacturer For repairs contact your local B E G Br ck Electronic subsidiary or directly B E G Br ck Electronic GmbH Germany 7 3 Disposing For disposal observe the...

Page 25: ...n on threshold is not set correctly Correct threshold Correct detection sensitivity The luminaire remains permanently switched on Permanent movements of heat sources in the detection area Remove heat...

Page 26: ...e product to be traced in the event of a warranty complaint The product code of the BL4 and BL4 C is lasered into the housing of the basic unit 9 2 Contact details Service hotline 49 0 2266 90121 0 Mo...

Page 27: ...4 m max 5 m max 32 0 m max 16 0 m Monitored area when moving across the detector 284 m2 at 2 5 m mounting height 200 m2 at 2 5 m mounting height Switch on threshold 10 2000 Lux Follow up time 15 s 60...

Page 28: ...Operating Manual BL4 BL4 C 93288 93284 26 10 2 Dimensioned drawings 10 2 1 Ceiling installation 10 2 2 Surface mounting with mounting set 93183 15 19 5 4 5 51 12max 4 5 40 3 87 10 34 39 109...

Page 29: ...BL4 BL4 C 93288 93284 Operating Manual 27 10 2 3 Flush mounting with mounting set 93194 10 2 4 Wire basket BSK 92199 212 13 6 90 200 53...

Page 30: ...on of the use of certain hazardous substances in electrical and electronic equipment 2011 65 EU Art No Designation 93055 Remote control IR BL 93183 Mounting set surface mounted 93194 Mounting set flus...

Page 31: ...93284_93288_OP_MAN_BL4_en_V2 book 24 09 2020...

Reviews: