QUICK START

GUIDE

Document Number: 710-11426-00_ZXTx-RM_2117qsg

Recommended Accessories

Conduit Mounting Kit

# ZXTMT

Before you begin, be  

sure you have the following:

ZXT24-RM

ZXT9-RM

Zlinx

 Xtreme Radio Modem

+ Zlinx Radio Modem (ZXT24-RM or ZXT9-RM)

+ CD (w/Zlinx Manager Software, Manual)

+ Mounting Ears and Hardware

Required - sold separately:

+ 10-30 VDC Power Supply (not included)

+ USB Cable (not included)

+ Conduit Mounting Accessories (not included):

 

_Conduit Accessories

 

_Cable Gland

IP67 Power Supply, 24VDC, 60W

Panel Mount

# CLG-60-24

Configure and Wire to Match

Serial Devices

8

Configure serial settings on the 

Basic Modem Settings

 tab to match your serial 

device. 

Configure the DIP Switch to match your serial device.

Figure 5. Serial Settings - DIP Switch Configuration

(Wiring examples are located in the manual. See Step 4 for terminal block layout.)

Terminal Block Signal Direction:

o  RS-232 (modem is a DCE device):

  TD – Input, RD – Output, RTS – Input, CTS – Output.

o  RS-422/485 Four Wire:

  TDA(-)/TDB(+) – Output, RDA(-)/RDB(+) - Input

o  RS-485 2-Wire :

   A(-) and B(+) Signals are tied together by 

   the DIP Switch and are bi-directional.

You are now ready for field installation.

UL Class 1 / Division 2

9

Operating Voltage – 10 to 30 VDC

WARNING

- SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C 

AND D HAZARDOUS LOCATIONS, OR NONHAZARDOUS LOCATIONS ONLY.

WARNING - EXPLOSION HAZARD

 - SUBSTITUTION OF ANY COMPONENT 

MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2.

WARNING - EXPLOSION HAZARD

 – WHEN IN HAZARDOUS LOCATIONS, 

TURN OFF POWER BEFORE REPLACING ANTENNA. 
Intended Use of Equipment – please see the B+B SmartWorx Data Sheets and 

Quick Start Guides for each Zlinx Xtreme product for explanations of the intended 

use of this equipment.
Wiring Terminals – Use Copper Wire Only, one conductor per terminal.
Wire Range 30 – 12 AWG.
Maximum Surrounding Ambient Air Temperature: 74°C
UL Class I, Division 2 Wiring Methods. The Zlinx Xtreme enclosure is provided with 

two conduit knockouts that serve as wiring provisions for Class I, Division 2 wiring 

methods per the National Electrical Code (NEC).

MANUFACTURER TYPE

Relay Case and Base

Mitsubishi Engineering 

Plastics Corp.

5010GN6-30M8AM

Sealant

Three Bond Ltd.

TB2225G

The following instructions include procedures to be followed in order to ensure UL 

“separation between circuits” as defined in the NEC:
The low-voltage (LV) wiring – DC power, analog & digital signals – must be separated 

from the high voltage (HV) wiring for the relay contacts. In all cases HV wiring must be 

rated minimum 250V. 
Separation between circuits can be accomplished by using one of the three following 

methods:

a. Use one conduit knockout to route LV wiring and the second conduit knockout to 

route the HV wiring, OR see methods 2 and 3 below.
The remaining two methods use one conduit knockout for all wiring. In this case, a 

UL Recognized (UL type QCRV2) conduit plug must be used per the NEC to plug 

the second conduit knockout.

b. Enclose LV wiring in a 250V rated insulated sheath to separate it from the HV 

wiring, OR

c. Use 250VAC rated wires for both LV and HV wiring.

Temperature rating of field installed conductors - Field conductors shall be rated 

60

°

C/75

°

C minimum (either are acceptable) and sized accordingly. 

When conduit openings are not being used, a UL Recognized plug (type QCRV2) 

shall be used.
The following is UL-required information regarding the Sealed Relay Devices:

WARNING

 – Exposure to some chemicals may degrade the sealing properties of 

materials used in the Sealed Relay Device.

RECOMMENDATION

 – It is recommended to inspect the sealed relay device 

periodically and to check for any degradation of the materials and to replace the 

component product, not the sealed device, if any degradation is found.

Sealed Relay Device Information:

Sealed Device: Relay Models G6RL-14-ASI-DC5, G6RL-14-ASI-DC6, G6RL-14-SR-

ASI-DC5 or G6RL-14-SR-ASI-DC6 manufactured by Omron Corp.