Product Overview

UL Installation Guide

Terminal Block

Baud Rates

Wire the Converter

1

3

2

4

Fiber

Connectors

Terminal

Blocks

LEDs

DIP Switch

Underwriters Laboratories Conditions of Acceptability –

When installed in the end-use equipment, consideration

should be given to the following:

1. The wiring terminals are suitable for factory wiring only.

2. This device is to be mounted in a suitable enclosure in 

the end-product.

3. This device is suitable for operation at a maximum

surrounding air temperature as described in the 

documentation.

4. These devices are intended for use in a pollution

degree 2 environment.

  -Input Voltage: 10 – 30 VDC

  - Input Power 4.2 Watts

  - Wire Range: 12 – 24 AWG

  - Tightening Torque: 4 kgf-cm

  - Temperature rating of filed installed conductors is

  105 C minimum, sized for 60 C ampacity.

  - Use copper wire only

  -  Maximum surrounding ambient air temperature

  80 C

RS-232

RS-485 2 Wire

RS-422/RS-485 4 Wire

Fiber Optic

Terminal

Signal

A

RS-232 RD (OUTPUT)

B

GND

C

GND

D

RS-232 TD (INPUT)

E

NOT CONNECTED

F

+10 TO 30 VDC

G

RS-422/485 TDA ( - ) / DATA A ( - )

H

RS-422/485 TDB (+) / DATA B (+)

J

+10 TO 30 VDC

K

RS-422/485 RDA ( - ) / DATA A ( - )

L

RS-422/485 RDB (+) / DATA B (+)

Baud

1

2

3

4

5

4800

OFF

OFF

OFF

OFF

ON

9600

OFF

OFF

OFF

ON

OFF

19.2K

OFF

OFF

ON

OFF

OFF

38.4K

OFF

ON

OFF

OFF

OFF

57.6K

ON

OFF

OFF

OFF

OFF

76.8K

ON

OFF

ON

ON

OFF

115.2K

ON

ON

ON

OFF

OFF