Operation
Azbil Corporation
2-74
Model SLX 110/120 - Smart displacement type level transmitter
2-7 :
Operation of external adjustment switch (with indicator)
Data can be read by the SFC even while the external adjustment switch is in
operation. What is read is data immediately before the adjustment mode was entered.
~Note:
•
If an SFC communication has been started while operating the external
adjustment switch, adjustment will be stopped as long as the communication
continues.
•
In the case of the DE output mode, the external adjustment switch cannot be used.
•
The change is reflected in the output after the normal condition is recovered from
the adjustment mode.
•
Do not use a magnetic driver because this may prevent accurate adjustment.
•
In the case of an engineering unit (real scale) display format, it may take a few
seconds after each adjustment mode is entered until a correct value is displayed.
•
Start operation after correct value appears.
+
-
Switch
Figure 2-8 Switch position
Basic operation method
While pushing in the switch toward the back using a flat-head screwdriver, turn the
switch clockwise (+) or counterclockwise (-).
Function
•
Zero adjustment to adjust to real level (pinpoint adjustment)
• Damping adjustment
•
Zero span adjustment
The operation sequence of the entire external adjustment switch is given on
Summary of Contents for SLX 110
Page 1: ...Smart Displacement type Level Transmitter Model SLX 110 120 User s Manual CM2 SLX100 2001...
Page 4: ......
Page 8: ...iv Model SLX 110 120 Smart displacement type level transmitter...
Page 120: ...Operation Azbil Corporation 2 80 Model SLX 110 120 Smart displacement type level transmitter...
Page 150: ...Maintenance Azbil Corporation 3 30 Model SLX 110 120 Smart displacement type level transmitter...
Page 162: ...Azbil Corporation 5 2 Model SLX 110 120 Smart displacement type level transmitter...
Page 163: ......
Page 166: ......
Page 168: ......